By continuing to use the website, you will be agreed with ETK Kablo’s use of cookies, GDPR and other policies.
x

Products

RE-2Y(St)H-TP

» At instrumentation control and data processes,analog and digital signal transmission.
» In chemical and petrochemical industry.
» Powerplants.
» In indoor environments intensely populatedby people, where there is electromagneticinterference.
» Outdoor and indoor places,dry, moist and wetplaces.
» Gas stations, water transportation systems.
1 - Conductor : Stranded electrolytic copper conductor (Class 2) (IEC 60228, EN 60228, DIN VDE 0295)
2 - Insulation : Polyethylene (BS EN 50290-2, VDE 0207 YI1), Black, White; Number coded (BS 5308-2)
3 - Stranding : Pairs are stranded in layers.
4 - Wrapping : Polyester tape
5 - Screen : Tinned copper earthing wire, Al/PET tape
6 - Outer Jacket : UV resistant halogen-free outer jacket. RAL 9004 (Black)
Cross SectionConductor Resistance
Ω/km
(20 °C)
Insulation Resistance
M Ω/km
(20 °C)
Mutual Capacitance
nF/km
Operating Voltage
V
(DC)
Test Voltage
V (DC)
1 minute)
0.50 mm²36.050001603002000
0.75 mm²24.550001603002000
1.00 mm²18.150001603002000
1.50 mm²12.150001703002000
2.50 mm²7.4150001705002500
Part NumberPair CountConductor Cross-section (mm²)Approx. Cable Diameter (mm)Copper Weight (kg/km)Approx. Weight (kg/km)Packing Lengths (m)
3.562.1.1.3.0050.0.000110,55,61444100/500/1000
3.562.1.1.3.0050.0.000220,57,92468100/500/1000
3.562.1.1.3.0050.0.000440,59,44398100/500/1000
3.562.1.1.3.0050.0.000880,512,481175100/500/1000
3.562.1.1.3.0050.0.0010100,514,0100214100/500/1000
3.562.1.1.3.0050.0.0012120,514,3118242100/500/1000
3.562.1.1.3.0050.0.0016160,516,4156319100/500/1000
3.562.1.1.3.0050.0.0020200,518,3194380100/500/1000
3.562.1.1.3.0050.0.0024240,519,9232451100/500/1000


Part NumberPair CountConductor Cross-section (mm²)Approx. Cable Diameter (mm)Copper Weight (kg/km)Approx. Weight (kg/km)Packing Lengths (m)
3.562.1.1.3.0075.0.000110,756,01949100/500/1000
3.562.1.1.3.0075.0.000220,759,03486100/500/1000
3.562.1.1.3.0075.0.000440,7510,063123100/500/1000
3.562.1.1.3.0075.0.000880,7513,6120225100/500/1000
3.562.1.1.3.0075.0.0010100,7515,3149272100/500/1000
3.562.1.1.3.0075.0.0012120,7515,8178310100/500/1000
3.562.1.1.3.0075.0.0016160,7518,0235410100/500/1000
3.562.1.1.3.0075.0.0020200,7520,2293500100/500/1000
3.562.1.1.3.0075.0.0024240,7522,0350600100/500/1000


Part NumberPair CountConductor Cross-section (mm²)Approx. Cable Diameter (mm)Copper Weight (kg/km)Approx. Weight (kg/km)Packing Lengths (m)
3.562.1.1.3.0100.0.0001116,42457100/500/1000
3.562.1.1.3.0100.0.0002219,24498100/500/1000
3.562.1.1.3.0100.0.00044111,083155100/500/1000
3.562.1.1.3.0100.0.00088114,7160275100/500/1000
3.562.1.1.3.0100.0.001010116,8199345100/500/1000
3.562.1.1.3.0100.0.001212117,0238394100/500/1000
3.562.1.1.3.0100.0.001616119,9316530100/500/1000
3.562.1.1.3.0100.0.002020122,0393635100/500/1000


Part NumberPair CountConductor Cross-section (mm²)Approx. Cable Diameter (mm)Copper Weight (kg/km)Approx. Weight (kg/km)Packing Lengths (m)
3.562.1.1.3.0130.0.000111,36,83088100/500/1000
3.562.1.1.3.0130.0.000221,310,055119100/500/1000
3.562.1.1.3.0130.0.000441,311,8106184100/500/1000
3.562.1.1.3.0130.0.000881,315,8207335100/500/1000
3.562.1.1.3.0130.0.0010101,318,0257410100/500/1000
3.562.1.1.3.0130.0.0012121,318,6308476100/500/1000
3.562.1.1.3.0130.0.0016161,321,3408630100/500/1000
3.562.1.1.3.0130.0.0020201,36,8509775100/500/1000


Part NumberPair CountConductor Cross-section (mm²)Approx. Cable Diameter (mm)Copper Weight (kg/km)Approx. Weight (kg/km)Packing Lengths (m)
3.562.1.1.3.0150.0.000111,57,23369100/500/1000
3.562.1.1.3.0150.0.000221,510,562130100/500/1000
3.562.1.1.3.0150.0.000441,512,3119210100/500/1000
3.562.1.1.3.0150.0.000881,517,0232380100/500/1000
3.562.1.1.3.0150.0.0010101,519,2289470100/500/1000
3.562.1.1.3.0150.0.0012121,520,0346545100/500/1000
3.562.1.1.3.0150.0.0016161,522,8459710100/500/1000
3.562.1.1.3.0150.0.0020201,57,2573880100/500/1000


Part NumberPair CountConductor Cross-section (mm²)Approx. Cable Diameter (mm)Copper Weight (kg/km)Approx. Weight (kg/km)Packing Lengths (m)
3.562.1.1.3.0250.0.000112,58,952130100/500/1000
3.562.1.1.3.0250.0.000222,511,999338100/500/1000
3.562.1.1.3.0250.0.000442,515,3194617100/500/1000
3.562.1.1.3.0250.0.000882,519,5382765100/500/1000
3.562.1.1.3.0250.0.0010102,521,5476901100/500/1000
3.562.1.1.3.0250.0.0012122,523,65711170100/500/1000
3.562.1.1.3.0250.0.0016162,527,27591435100/500/1000
3.562.1.1.3.0250.0.0020202,530,29481731100/500/1000
Bending RadiusTemperature Range
Operating
7.5xD mm-30°C~+70°C