• Feeder cable for frequency controlled motors with electromagnetic interference. |
• At instrumentation and control engineering. |
• At industrial electronics. |
• Computer and office devices. |
• Indoor communication systems. |
• Indoor sound systems. |
1 - Conductor | : | Stranded electrolytic copper conductor (Class 5) (IEC 60228, EN 60228, DIN VDE 0295) |
2 - Insulation | : | PVC (TS IEC 60189-2, EN 50290-2-21) (DIN 47100) |
3 - Stranding | : | Screened pairs or triads are stranded in layers. |
4 - Individual Wrapping | : | Polyester tape |
5 - Individual Screen | : | Tinned copper earthing wire, Al/PET tape |
6 - Wrapping | : | Polyester tape |
7 - Screen | : | Al/PET tape, tinned copper braiding |
8 - Inner Jacket | : | UV resistant PVC inner jacket. RAL 7035 (Grey) |
9 - Armor | : | Galvanized steel wire braiding |
10 - Outer Jacket | : | UV resistant PVC outer jacket. RAL 7035 (Grey) |
Cross Section | Conductor Resistance (20 °C) Ω/km | Insulation Resistance (20 °C) MΩ/km | Mutual Capacitance nF/km | Operating Voltage V DC | Test Voltage (@ 1 minute) V DC |
---|---|---|---|---|---|
0.22 mm² | 85.0 | 200 | 110 | 250 | 1200 |
0.25 mm² | 77.8 | 200 | 110 | 250 | 1200 |
0.34 mm² | 56.0 | 200 | 110 | 250 | 1200 |
0.50 mm² | 39.0 | 20 | 120 | 300/500 | 2000 |
0.75 mm² | 26.0 | 20 | 120 | 300/500 | 2000 |
1.00 mm² | 19.5 | 20 | 130 | 300/500 | 2000 |
1.50 mm² | 13.3 | 20 | 140 | 300/500 | 2000 |
2.50 mm² | 7.98 | 20 | 150 | 300/500 | 2000 |
Flame Retardancy Test |
---|
IEC 60332-1-2, VDE 0482-332-1-2, BS EN 60332-1-2 |
Bending Radius | Temperature Range Operating |
---|---|
7.5xD mm | -30°C ~ +70°C |