RE-2Y(St)Yv-TP

» At instrumentation control and data processes,analog and digital signal transmission.
» In chemical and petrochemical industry.
» Powerplants.
» Gas stations, water transportation systems.
1 - Conductor : Stranded electrolytic copper conductor (Class 2) (IEC 60228, EN 60228, DIN VDE 0295)
2 - Insulation : Polyethylene (BS EN 50290-2, VDE 0207 YI1), Black, White; Number coded (BS 5308-2)
3 - Stranding : Pairs are stranded in layers.
4 - Wrapping : Polyester tape
5 - Screen : Tinned copper earthing wire, Al/PET tape
6 - Outer Jacket : UV resistant PVC outer jacket. RAL 9005 (Black)
Cross
Section
Conductor Resistance
Ω/km (20 °C)
Insulation Resistance
MΩ/km (20 °C)
Mutual Capacitance
pF/m
Inductance/Resistance
Ratio
nH/Ω
Current Carrying
Capacity
A
Operating Voltage
V DC
Test Voltage
V (DC.
1 minute)
Pair-Pair
Test Voltage
V (DC.
1 minute)
Pair-Screen
0.50 mm²36500065256300/50020002000
0.75 mm²24,55000652513300/50020002000
1.00 mm²18,15000652516300/50020002000
1.30 mm²13,95000754018300/50020002000
1.5 mm²12,15000754020300/50020002000
2.5 mm²7,415000756025300/50020002000
Part NumberPair CountConductor Cross-section (mm²)Approx. Cable Diameter (mm)Copper Weight (kg/km)Approx. Weight (kg/km)Packing Lengths (m)
3.566.1.1.2.0050.0.000110,57,21470100/500/1000
3.566.1.1.2.0050.0.000220,59,22496100/500/1000
3.566.1.1.2.0050.0.000440,51143130100/500/1000
3.566.1.1.2.0050.0.000880,513,381200100/500/1000
3.566.1.1.2.0050.0.0010100,514,2100235100/500/1000
3.566.1.1.2.0050.0.0012120,515,2118264100/500/1000
3.566.1.1.2.0050.0.0016160,517,1156340100/500/1000
3.566.1.1.2.0050.0.0020200,519,0194395100/500/1000
3.566.1.1.2.0050.0.0024240,520,8232470100/500/1000


Part NumberPair CountConductor Cross-section (mm²)Approx. Cable Diameter (mm)Copper Weight (kg/km)Approx. Weight (kg/km)Packing Lengths (m)
3.566.1.1.2.0075.0.000110,756,81985100/500/1000
3.566.1.1.2.0075.0.000220,759,134110100/500/1000
3.566.1.1.2.0075.0.000440,7511,263165100/500/1000
3.566.1.1.2.0075.0.000880,7514,8120265100/500/1000
3.566.1.1.2.0075.0.0010100,7516,5149315100/500/1000
3.566.1.1.2.0075.0.0012120,7517,0178340100/500/1000
3.566.1.1.2.0075.0.0016160,7519,2235430100/500/1000
3.566.1.1.2.0075.0.0020200,7521,5293515100/500/1000
3.566.1.1.2.0075.0.0024240,7523,5350600100/500/1000


Part NumberPair CountConductor Cross-section (mm²)Approx. Cable Diameter (mm)Copper Weight (kg/km)Approx. Weight (kg/km)Packing Lengths (m)
3.566.1.1.2.0100.0.0001117,22482100/500/1000
3.566.1.1.2.0100.0.00022110,444130100/500/1000
3.566.1.1.2.0100.0.00044112,283195100/500/1000
3.566.1.1.2.0100.0.00088116,0160315100/500/1000
3.566.1.1.2.0100.0.001010118,0199375100/500/1000
3.566.1.1.2.0100.0.001212118,8238430100/500/1000
3.566.1.1.2.0100.0.001616121,2316530100/500/1000
3.566.1.1.2.0100.0.002020123,5393640100/500/1000


Part NumberPair CountConductor Cross-section (mm²)Approx. Cable Diameter (mm)Copper Weight (kg/km)Approx. Weight (kg/km)Packing Lengths (m)
3.566.1.1.2.0130.0.000111,37,93098100/500/1000
3.566.1.1.2.0130.0.000221,311,255155100/500/1000
3.566.1.1.2.0130.0.000441,313,0106235100/500/1000
3.566.1.1.2.0130.0.000881,317,0207390100/500/1000
3.566.1.1.2.0130.0.0010101,319,4257485100/500/1000
3.566.1.1.2.0130.0.0012121,320,0308550100/500/1000
3.566.1.1.2.0130.0.0016161,323,0408640100/500/1000
3.566.1.1.2.0130.0.0020201,325,2509800100/500/1000


Part NumberPair CountConductor Cross-section (mm²)Approx. Cable Diameter (mm)Copper Weight (kg/km)Approx. Weight (kg/km)Packing Lengths (m)
3.566.1.1.2.0150.0.000111,58,333115100/500/1000
3.566.1.1.2.0150.0.000221,511,762170100/500/1000
3.566.1.1.2.0150.0.000441,513,6119240100/500/1000
3.566.1.1.2.0150.0.000881,518,3232415100/500/1000
3.566.1.1.2.0150.0.0010101,520,5289520100/500/1000
3.566.1.1.2.0150.0.0012121,521,5346590100/500/1000
3.566.1.1.2.0150.0.0016161,524,0459800100/500/1000
3.566.1.1.2.0150.0.0020201,527,05731100100/500/1000


Part NumberPair CountConductor Cross-section (mm²)Approx. Cable Diameter (mm)Copper Weight (kg/km)Approx. Weight (kg/km)Packing Lengths (m)
3.566.1.1.2.0250.0.000112,59,252127100/500/1000
3.566.1.1.2.0250.0.000222,513,299207100/500/1000
3.566.1.1.2.0250.0.000442,515,3194342100/500/1000
3.566.1.1.2.0250.0.000882,519,8382650100/500/1000
3.566.1.1.2.0250.0.0010102,523476776100/500/1000
3.566.1.1.2.0250.0.0012122,525,2571914100/500/1000
3.566.1.1.2.0250.0.0016162,527,17591190100/500/1000
3.566.1.1.2.0250.0.0020202,528,09481620100/500/1000


Bending RadiusTemperature Range
Operating
7.5xD mm-30°C~+70°C
Notes:
Electromagnetic compatability (EMC)