• At instrumentation control and data processes, analogand digital signal transmission. |
• In chemical and petrochemical industry. |
• Powerplants. |
• In indoor environments intensely populatedby people, where there is electromagneticinterference. |
• Outdoor and indoor places,dry, moist and wet places. |
• Gas stations, water transportation systems. |
1 - Conductor | : | Stranded electrolytic copper conductor (Class 2) (IEC 60228, EN 60228, DIN VDE 0295) |
2 - Insulation | : | XLPE (BS EN 50290-2, VDE 0207 YI1), Black, White, Red; Number coded (BS 5308-2) |
3 - Individual Stranding | : | Insulations stranding into pairs or triads |
4 - Individual Wrapping | : | Polyester tape |
5 - Individual Screen | : | Tinned copper earthing wire, Al/PET tape |
6 - Overall Stranding | : | Screened pairs or triads are stranded in layers. |
7 - Overall Wrapping | : | Polyester tape |
8 - Overall Screen | : | Tinned copper earthing wire, Al/PET tape |
9 - Inner Jacket | : | Halogen-free inner jacket. RAL 9005 (Black) |
10 - Armor | : | Galvanized steel wire armor, polyester tape |
11 - Outer Jacket | : | UV resistant halogen-free outer jacket. RAL 9005 (Black) |
Conductor Diameter | Conductor Resistance Ω/km (20 °C) | Insulation Resistance (@500V DC) MΩ/km | Mutual Capacitance nF/km | Operating Voltage V DC | Test Voltage (@ 1 minute) V DC |
---|---|---|---|---|---|
0.50 mm² | 36.0 | Min. 1000 | Max. 250 | 300/500 | 2000 |
0.75 mm² | 24.5 | Min. 1000 | Max. 250 | 300/500 | 2000 |
1.00 mm² | 18.1 | Min. 1000 | Max. 250 | 300/500 | 2000 |
1.50 mm² | 12.1 | Min. 1000 | Max. 250 | 300/500 | 2000 |
2.50 mm² | 7.41 | Min. 1000 | Max. 250 | 300/500 | 2000 |
Manufacturing Referance | Smoke Density Test | Corrosive Gas Test | Halogen-free Test | Flame Propagation Test | Flame Retardancy Test |
---|---|---|---|---|---|
EN 50288-7 or IEC 60502-1 | IEC 61034-2, VDE 0482-1034-2, BS EN 61034-2 | IEC 60754-2, VDE 0482-267-2-3, BS EN 50267-2-3 | IEC 60754-1, VDE 0482-267-2-1, BS EN 50267-2-1 | IEC 60332-3-24, VDE 0482-332-3-24, EN 60332-2-24 | IEC 60332-1-2, VDE 0482-332-1-2, BS EN 60332-1-2 |
Bending Radius | Temperature Range Operating |
---|---|
7.5xD mm | -30°C ~ +90°C |