By continuing to use the website, you will be agreed with ETK Kablo’s use of cookies, GDPR and other policies.
x

Products

RE-H(St)HSWBH

• At instrumentation control and data processes, analogand digital signal transmission.
• In chemical and petrochemical industry.
• Powerplants.
• In indoor environments intensely populatedby people, where there is electromagneticinterference.
• Outdoor and indoor places,dry, moist and wet places.
• Gas stations, water transportation systems.
1 - Conductor:Stranded electrolytic copper conductor (Class 2) (IEC 60228, EN 60228, DIN VDE 0295)
2 - Insulation:Halogen-free (BS EN 50290-2, VDE 0207 YI1), White; Number coded (BS 5308-2)
3 - Stranding:In layers
4 - Wrapping:Polyester tape
5 - Screen:Tinned copper earthing wire, Al/PET tape
6 - Inner Jacket:Halogen-free inner jacket. RAL 9005 (Black)
7 - Armor:Galvanized steel wire braiding
8 - Outer Jacket:UV resistant halogen-free outer jacket. RAL 9005 (Black)
Conductor
Diameter
Conductor Resistance
Ω/km
(20 °C)
Insulation
Resistance
(@500V DC)
MΩ/km
Mutual Capacitance

nF/km
Operating
Voltage

V DC
Test Voltage

(@ 1 minute)
V DC
0.50 mm²36.0100100300/5002000
0.75 mm²24.5100100300/5002000
1.00 mm²18.1100100300/5002000
1.50 mm²12.1100100300/5002000
2.50 mm²7.41100100300/5002000
Manufacturing ReferanceSmoke Density TestCorrosive Gas TestHalogen-free TestFlame Propagation TestFlame Retardancy Test
EN 50288-7
or
IEC 60502-1
IEC 61034-2,
VDE 0482-1034-2,
BS EN 61034-2
IEC 60754-2,
VDE 0482-267-2-3,
BS EN 50267-2-3
IEC 60754-1,
VDE 0482-267-2-1,
BS EN 50267-2-1
IEC 60332-3-24,
VDE 0482-332-3-24,
EN 60332-2-24
IEC 60332-1-2,
VDE 0482-332-1-2,
BS EN 60332-1-2
Bending RadiusTemperature Range
Operating
7.5xD mm-30°C ~ +70°C