• At instrumentation control and data processes, analogand digital signal transmission. |
• In chemical and petrochemical industry. |
• Powerplants. |
• Outdoor and indoor places,dry, moist and wet places. |
• Gas stations, water transportation systems. |
1 - Conductor | : | Stranded electrolytic copper conductor (Class 2) (IEC 60228, EN 60228, DIN VDE 0295) |
2 - Insulation | : | PVC (BS EN 50290-2, VDE 0207 YI1), Black, White, Red; Number coded (BS 5308-2) |
3 - Stranding | : | Insulations stranding into pairs or triads |
4 - Wrapping | : | Polyester tape |
5 - Screen | : | Tinned copper earthing wire, Al/PET tape |
6 - Outer Jacket | : | UV resistant PVC outer jacket. RAL 9005 (Black) |
Conductor Diameter | Conductor Resistance Ω/km (20 °C) | Insulation Resistance (@500V DC) MΩ/km | Mutual Capacitance nF/km | Operating Voltage V DC | Test Voltage (@ 1 minute) V DC |
---|---|---|---|---|---|
0.50 mm² | 36.0 | 100 | 160 | 300/500 | 2000 |
0.75 mm² | 24.5 | 100 | 160 | 300/500 | 2000 |
1.00 mm² | 18.1 | 100 | 170 | 300/500 | 2000 |
1.50 mm² | 12.1 | 100 | 170 | 300/500 | 2000 |
2.50 mm² | 7.41 | 100 | 170 | 300/500 | 2000 |
Manufacturing Referance | Flame Retardancy Test |
---|---|
EN 50288-7 or IEC 60502-1 | IEC 60332-1-2 |
Part Number | Pair Count | Conductor Cross-section (mm²) | Approx. Cable Diameter (mm) | Copper Weight (kg/km) | Approx. Weight (kg/km) | Packing Lengths (m) |
---|---|---|---|---|---|---|
3.562.1.2.2.0050.0.0001 | 1 | 0,5 | 5,6 | 14 | 45 | 100/500/1000 |
3.562.1.2.2.0050.0.0002 | 2 | 0,5 | 8,2 | 24 | 60 | 100/500/1000 |
3.562.1.2.2.0050.0.0004 | 4 | 0,5 | 9,4 | 43 | 100 | 100/500/1000 |
3.562.1.2.2.0050.0.0008 | 8 | 0,5 | 12,3 | 81 | 186 | 100/500/1000 |
3.562.1.2.2.0050.0.0010 | 10 | 0,5 | 14,0 | 100 | 231 | 100/500/1000 |
3.562.1.2.2.0050.0.0012 | 12 | 0,5 | 14,3 | 118 | 263 | 100/500/1000 |
3.562.1.2.2.0050.0.0016 | 16 | 0,5 | 16,4 | 156 | 344 | 100/500/1000 |
3.562.1.2.2.0050.0.0020 | 20 | 0,5 | 18,3 | 194 | 414 | 100/500/1000 |
3.562.1.2.2.0050.0.0024 | 24 | 0,5 | 19,9 | 232 | 492 | 100/500/1000 |
Part Number | Pair Count | Conductor Cross-section (mm²) | Approx. Cable Diameter (mm) | Copper Weight (kg/km) | Approx. Weight (kg/km) | Packing Lengths (m) |
---|---|---|---|---|---|---|
3.562.1.2.2.0075.0.0001 | 1 | 0,75 | 6,0 | 19 | 50 | 100/500/1000 |
3.562.1.2.2.0075.0.0002 | 2 | 0,75 | 9,0 | 34 | 80 | 100/500/1000 |
3.562.1.2.2.0075.0.0004 | 4 | 0,75 | 10,0 | 63 | 120 | 100/500/1000 |
3.562.1.2.2.0075.0.0008 | 8 | 0,75 | 13,6 | 120 | 240 | 100/500/1000 |
3.562.1.2.2.0075.0.0010 | 10 | 0,75 | 15,3 | 149 | 290 | 100/500/1000 |
3.562.1.2.2.0075.0.0012 | 12 | 0,75 | 15,8 | 178 | 330 | 100/500/1000 |
3.562.1.2.2.0075.0.0016 | 16 | 0,75 | 18,0 | 235 | 440 | 100/500/1000 |
3.562.1.2.2.0075.0.0020 | 20 | 0,75 | 20,2 | 293 | 540 | 100/500/1000 |
3.562.1.2.2.0075.0.0024 | 24 | 0,75 | 22,0 | 350 | 635 | 100/500/1000 |
Part Number | Pair Count | Conductor Cross-section (mm²) | Approx. Cable Diameter (mm) | Copper Weight (kg/km) | Approx. Weight (kg/km) | Packing Lengths (m) |
---|---|---|---|---|---|---|
3.562.1.2.2.0100.0.0001 | 1 | 1 | 6,4 | 24 | 58 | 100/500/1000 |
3.562.1.2.2.0100.0.0002 | 2 | 1 | 9,2 | 44 | 100 | 100/500/1000 |
3.562.1.2.2.0100.0.0004 | 4 | 1 | 11,0 | 83 | 160 | 100/500/1000 |
3.562.1.2.2.0100.0.0008 | 8 | 1 | 14,7 | 160 | 295 | 100/500/1000 |
3.562.1.2.2.0100.0.0010 | 10 | 1 | 16,8 | 199 | 350 | 100/500/1000 |
3.562.1.2.2.0100.0.0012 | 12 | 1 | 17,0 | 238 | 420 | 100/500/1000 |
3.562.1.2.2.0100.0.0016 | 16 | 1 | 19,9 | 316 | 560 | 100/500/1000 |
3.562.1.2.2.0100.0.0020 | 20 | 1 | 22,0 | 393 | 680 | 100/500/1000 |
Part Number | Pair Count | Conductor Cross-section (mm²) | Approx. Cable Diameter (mm) | Copper Weight (kg/km) | Approx. Weight (kg/km) | Packing Lengths (m) |
---|---|---|---|---|---|---|
3.562.1.2.2.0130.0.0001 | 1 | 1,3 | 6,8 | 30 | 64 | 100/500/1000 |
3.562.1.2.2.0130.0.0002 | 2 | 1,3 | 10,0 | 55 | 115 | 100/500/1000 |
3.562.1.2.2.0130.0.0004 | 4 | 1,3 | 11,8 | 106 | 195 | 100/500/1000 |
3.562.1.2.2.0130.0.0008 | 8 | 1,3 | 15,8 | 207 | 350 | 100/500/1000 |
3.562.1.2.2.0130.0.0010 | 10 | 1,3 | 18,0 | 257 | 440 | 100/500/1000 |
3.562.1.2.2.0130.0.0012 | 12 | 1,3 | 18,6 | 308 | 505 | 100/500/1000 |
3.562.1.2.2.0130.0.0016 | 16 | 1,3 | 21,3 | 408 | 650 | 100/500/1000 |
3.562.1.2.2.0130.0.0020 | 20 | 1,3 | 24,0 | 509 | 820 | 100/500/1000 |
Part Number | Pair Count | Conductor Cross-section (mm²) | Approx. Cable Diameter (mm) | Copper Weight (kg/km) | Approx. Weight (kg/km) | Packing Lengths (m) |
---|---|---|---|---|---|---|
3.562.1.2.2.0150.0.0001 | 1 | 1,5 | 7,2 | 33 | 70 | 100/500/1000 |
3.562.1.2.2.0150.0.0002 | 2 | 1,5 | 10,5 | 62 | 135 | 100/500/1000 |
3.562.1.2.2.0150.0.0004 | 4 | 1,5 | 12,3 | 119 | 220 | 100/500/1000 |
3.562.1.2.2.0150.0.0008 | 8 | 1,5 | 17,0 | 232 | 400 | 100/500/1000 |
3.562.1.2.2.0150.0.0010 | 10 | 1,5 | 19,2 | 289 | 495 | 100/500/1000 |
3.562.1.2.2.0150.0.0012 | 12 | 1,5 | 20,0 | 346 | 575 | 100/500/1000 |
3.562.1.2.2.0150.0.0016 | 16 | 1,5 | 22,8 | 459 | 760 | 100/500/1000 |
3.562.1.2.2.0150.0.0020 | 20 | 1,5 | 25,8 | 573 | 934 | 100/500/1000 |
Part Number | Pair Count | Conductor Cross-section (mm²) | Approx. Cable Diameter (mm) | Copper Weight (kg/km) | Approx. Weight (kg/km) | Packing Lengths (m) |
---|---|---|---|---|---|---|
3.562.1.2.2.0250.0.0001 | 1 | 2,5 | 8,9 | 52 | 110 | 100/500/1000 |
3.562.1.2.2.0250.0.0002 | 2 | 2,5 | 11,9 | 99 | 190 | 100/500/1000 |
3.562.1.2.2.0250.0.0004 | 4 | 2,5 | 15,3 | 194 | 330 | 100/500/1000 |
3.562.1.2.2.0250.0.0008 | 8 | 2,5 | 19,5 | 382 | 615 | 100/500/1000 |
3.562.1.2.2.0250.0.0010 | 10 | 2,5 | 21,5 | 476 | 765 | 100/500/1000 |
3.562.1.2.2.0250.0.0012 | 12 | 2,5 | 23,6 | 571 | 901 | 100/500/1000 |
3.562.1.2.2.0250.0.0016 | 16 | 2,5 | 27,2 | 759 | 1170 | 100/500/1000 |
3.562.1.2.2.0250.0.0020 | 20 | 2,5 | 30,2 | 948 | 1435 | 100/500/1000 |
Bending Radius | Temperature Range Operating |
---|---|
7.5xD mm | -30°C ~ +70°C |