By continuing to use the website, you will be agreed with ETK Kablo’s use of cookies, GDPR and other policies.
x

Products

RE-Y(St)Y-TP/TT

• At instrumentation control and data processes, analogand digital signal transmission.
• In chemical and petrochemical industry.
• Powerplants.
• Outdoor and indoor places,dry, moist and wet places.
• Gas stations, water transportation systems.
1 - Conductor:Stranded electrolytic copper conductor (Class 2) (IEC 60228, EN 60228, DIN VDE 0295)
2 - Insulation:PVC (BS EN 50290-2, VDE 0207 YI1), Black, White, Red; Number coded (BS 5308-2)
3 - Stranding:Insulations stranding into pairs or triads
4 - Wrapping:Polyester tape
5 - Screen:Tinned copper earthing wire, Al/PET tape
6 - Outer Jacket:UV resistant PVC outer jacket. RAL 9005 (Black)
Conductor
Diameter
Conductor Resistance
Ω/km
(20 °C)
Insulation
Resistance
(@500V DC)
MΩ/km
Mutual Capacitance

nF/km
Operating
Voltage

V DC
Test Voltage

(@ 1 minute)
V DC
0.50 mm²36.0100160300/5002000
0.75 mm²24.5100160300/5002000
1.00 mm²18.1100170300/5002000
1.50 mm²12.1100170300/5002000
2.50 mm²7.41100170300/5002000
Manufacturing ReferanceFlame Retardancy Test
EN 50288-7
or
IEC 60502-1
IEC 60332-1-2
Part NumberPair CountConductor Cross-section (mm²)Approx. Cable Diameter (mm)Copper Weight (kg/km)Approx. Weight (kg/km)Packing Lengths (m)
3.562.1.2.2.0050.0.000110,55,61445100/500/1000
3.562.1.2.2.0050.0.000220,58,22460100/500/1000
3.562.1.2.2.0050.0.000440,59,443100100/500/1000
3.562.1.2.2.0050.0.000880,512,381186100/500/1000
3.562.1.2.2.0050.0.0010100,514,0100231100/500/1000
3.562.1.2.2.0050.0.0012120,514,3118263100/500/1000
3.562.1.2.2.0050.0.0016160,516,4156344100/500/1000
3.562.1.2.2.0050.0.0020200,518,3194414100/500/1000
3.562.1.2.2.0050.0.0024240,519,9232492100/500/1000


Part NumberPair CountConductor Cross-section (mm²)Approx. Cable Diameter (mm)Copper Weight (kg/km)Approx. Weight (kg/km)Packing Lengths (m)
3.562.1.2.2.0075.0.000110,756,01950100/500/1000
3.562.1.2.2.0075.0.000220,759,03480100/500/1000
3.562.1.2.2.0075.0.000440,7510,063120100/500/1000
3.562.1.2.2.0075.0.000880,7513,6120240100/500/1000
3.562.1.2.2.0075.0.0010100,7515,3149290100/500/1000
3.562.1.2.2.0075.0.0012120,7515,8178330100/500/1000
3.562.1.2.2.0075.0.0016160,7518,0235440100/500/1000
3.562.1.2.2.0075.0.0020200,7520,2293540100/500/1000
3.562.1.2.2.0075.0.0024240,7522,0350635100/500/1000


Part NumberPair CountConductor Cross-section (mm²)Approx. Cable Diameter (mm)Copper Weight (kg/km)Approx. Weight (kg/km)Packing Lengths (m)
3.562.1.2.2.0100.0.0001116,42458100/500/1000
3.562.1.2.2.0100.0.0002219,244100100/500/1000
3.562.1.2.2.0100.0.00044111,083160100/500/1000
3.562.1.2.2.0100.0.00088114,7160295100/500/1000
3.562.1.2.2.0100.0.001010116,8199350100/500/1000
3.562.1.2.2.0100.0.001212117,0238420100/500/1000
3.562.1.2.2.0100.0.001616119,9316560100/500/1000
3.562.1.2.2.0100.0.002020122,0393680100/500/1000


Part NumberPair CountConductor Cross-section (mm²)Approx. Cable Diameter (mm)Copper Weight (kg/km)Approx. Weight (kg/km)Packing Lengths (m)
3.562.1.2.2.0130.0.000111,36,83064100/500/1000
3.562.1.2.2.0130.0.000221,310,055115100/500/1000
3.562.1.2.2.0130.0.000441,311,8106195100/500/1000
3.562.1.2.2.0130.0.000881,315,8207350100/500/1000
3.562.1.2.2.0130.0.0010101,318,0257440100/500/1000
3.562.1.2.2.0130.0.0012121,318,6308505100/500/1000
3.562.1.2.2.0130.0.0016161,321,3408650100/500/1000
3.562.1.2.2.0130.0.0020201,324,0509820100/500/1000


Part NumberPair CountConductor Cross-section (mm²)Approx. Cable Diameter (mm)Copper Weight (kg/km)Approx. Weight (kg/km)Packing Lengths (m)
3.562.1.2.2.0150.0.000111,57,23370100/500/1000
3.562.1.2.2.0150.0.000221,510,562135100/500/1000
3.562.1.2.2.0150.0.000441,512,3119220100/500/1000
3.562.1.2.2.0150.0.000881,517,0232400100/500/1000
3.562.1.2.2.0150.0.0010101,519,2289495100/500/1000
3.562.1.2.2.0150.0.0012121,520,0346575100/500/1000
3.562.1.2.2.0150.0.0016161,522,8459760100/500/1000
3.562.1.2.2.0150.0.0020201,525,8573934100/500/1000


Part NumberPair CountConductor Cross-section (mm²)Approx. Cable Diameter (mm)Copper Weight (kg/km)Approx. Weight (kg/km)Packing Lengths (m)
3.562.1.2.2.0250.0.000112,58,952110100/500/1000
3.562.1.2.2.0250.0.000222,511,999190100/500/1000
3.562.1.2.2.0250.0.000442,515,3194330100/500/1000
3.562.1.2.2.0250.0.000882,519,5382615100/500/1000
3.562.1.2.2.0250.0.0010102,521,5476765100/500/1000
3.562.1.2.2.0250.0.0012122,523,6571901100/500/1000
3.562.1.2.2.0250.0.0016162,527,27591170100/500/1000
3.562.1.2.2.0250.0.0020202,530,29481435100/500/1000
Bending RadiusTemperature Range
Operating
7.5xD mm-30°C ~ +70°C
Notes:
Electromagnetic compatability (EMC)