By continuing to use the website, you will be agreed with ETK Kablo’s use of cookies, GDPR and other policies.
x

JE-H(St)H Bd (FE180 / E30-E90 / PH120)

» Feeder cable for frequency controlled motors with electromagnetic interference.
» At instrumentation and control engineering.
» At industrial electronics.
» Computer and office devices.
» Indoor communication systems.
» Indoor sound systems.
» In places where human life, valuable materials and equipments need to be protected
1 - Conductor : Class 1 electrolytic solid copper (IEC 60228, DIN VDE 0295, EN 60228)
2 - Insulation : Cross-linked polymer compound in ceramic form (VDE 0815)
3 - Stranding : Insulations are stranded into pairs, four pairs are stranded together into groups, groups are stranded in layers.
4 - Wrapping : Polyester tape, glass yarn tape
5 - Screen : Tinned copper earthing wire, Al/PET tape
6 - Outer Jacket : UV resistant halogen-free outer jacket. RAL 2008 (Orange)
Conductor
Diameter
Conductor Resistance
Ω/km (20 °C)
Insulation Resistance
M Ω/km (500 V DC)
Mutual Capacitance
nF/km (800 Hz)
Operating Voltage
V DC

Test Voltage
V
(DC, 1 minute)

0.60 mm1301001003001000
0.80 mm73.21001003001000
1.0 mm44.61001003001000
1.5 mm²24.61001003001000
2.5 mm²15.11001003001000
Smoke Density TestCorrosive Gas TestHalogen-free TestFlame Retardancy TestFlame Propagation Test
IEC 61034-2,
VDE 0482-1034-2,
BS EN 61034-2
IEC 60754-2,
VDE 0482-267-2-3,
BS EN 50267-2-3
IEC 60754-1,
VDE 0482-267-2-1,
EN 50267-2-1,
BS EN 50267-2-1
IEC 60332-1-2,
VDE 0482-332-1-2,
BS EN 60332-1-2
IEC 60332-3-24,
VDE 0482-332-3-24,
BS EN 60332-3-24


Circuit Integrity Test
(FE180)
Circuit Integrity with Shock Test
(PH120)
Cable System Circuit Integrity Test
(E30 / E60 / E90)
IEC 60331-23EN 50200, VDE 0482-200, BS EN 50200DIN 4102-12 E30 / E90
Part NumberPair CountConductor Diameter (mm)Approx. Cable Diameter (mm)Copper Weight (kg/km)Approx. Weight (kg/km)Packing Lengths (m)
3.650.1.4.3.1080.0.000110,85.414.338100/500/1000
3.650.1.4.3.1080.0.000220,86.223.854100/500/1000
3.650.1.4.3.1080.0.000330,87.933.480100/500/1000
3.650.1.4.3.1080.0.000440,89.542.9103100/500/1000
3.650.1.4.3.1080.0.000550,89.852.4119100/500/1000
3.650.1.4.3.1080.0.000660,811.962144100/500/1000
3.650.1.4.3.1080.0.000880,812.381178100/500/1000
3.650.1.4.3.1080.0.0010100,812.8100.1208100/500/1000
Bending RadiusTemperature Range
Operating
10xD mm-40°C~+70°C
Notes:
Reference Standard: DIN VDE 0815