» Feeder cable for frequency controlled motors with electromagnetic interference.
» At instrumentation and control engineering.
» At industrial electronics.
» Computer and office devices.
» Indoor communication systems.
» Indoor sound systems.
» In places where human life, valuable materials and equipments need to be protected.
1 - Conductor : Stranded electrolytic copper conductor (Class 5) (IEC 60228, EN 60228, DIN VDE 0295)
2 - Insulation : Cross-linked polymer compound in ceramic form (DIN 47100)
3 - Stranding : Insulations are stranded into pairs and all pairs are stranded together.
4 - Wrapping : Polyester tape, glass yarn tape
5 - Outer Jacket : UV resistant halogen-free outer jacket. RAL 2008 (Orange)
Conductor
Diameter
Conductor Resistance
Ω/km (20 °C)
Insulation Resistance
M Ω/km (500 V DC)
Mutual Capacitance
nF/km (800 Hz)
Operating Voltage
V DC

Test Voltage
V
(DC, 1 minute)

0.50 mm²39201203002000
0.75 mm²26201203002000
1.00 mm²19.5201303002000
1.5 mm²13.3201403002000
2.5 mm²7.98201503002000
Smoke Density TestCorrosive Gas TestHalogen-free TestFlame Retardancy TestFlame Propagation Test
IEC 61034-2,
VDE 0482-1034-2,
BS EN 61034-2
IEC 60754-2,
VDE 0482-267-2-3,
BS EN 50267-2-3
IEC 60754-1,
VDE 0482-267-2-1,
EN 50267-2-1,
BS EN 50267-2-1
IEC 60332-1-2,
VDE 0482-332-1-2,
BS EN 60332-1-2
IEC 60332-3-24,
VDE 0482-332-3-24,
BS EN 60332-3-24


Circuit Integrity Test
(FE180)
Circuit Integrity with Shock Test
(PH120)
IEC 60331-23EN 50200, VDE 0482-200, BS EN 50200
Part NumberPair CountConductor Diameter (mm²)Approx. Cable Diameter (mm)Copper Weight (kg/km)Approx. Weight (kg/km)Packing Lengths (m)
3.513.2.4.3.0050.0.000110,55,48,934100/500/1000
3.513.2.4.3.0050.0.000220,5717,755100/500/1000
3.513.2.4.3.0050.0.000330,58,126,675100/500/1000
3.513.2.4.3.0050.0.000440,59,835,4101100/500/1000
3.513.2.4.3.0050.0.000550,510,344,3117100/500/1000
3.513.2.4.3.0050.0.000660,510,953,1137100/500/1000
3.513.2.4.3.0050.0.000770,511,962158100/500/1000
3.513.2.4.3.0050.0.000880,512,370,8175100/500/1000
3.513.2.4.3.0050.0.000990,51379,7195100/500/1000
3.513.2.4.3.0050.0.0010100,513,688,5212100/500/1000


Part NumberPair CountConductor Diameter (mm²)Approx. Cable Diameter (mm)Copper Weight (kg/km)Approx. Weight (kg/km)Packing Lengths (m)
3.513.2.4.3.0075.0.000110,755,913,342100/500/1000
3.513.2.4.3.0075.0.000220,757,826,671100/500/1000
3.513.2.4.3.0075.0.000330,75939,998100/500/1000
3.513.2.4.3.0075.0.000440,7510,953,1131100/500/1000
3.513.2.4.3.0075.0.000550,7511,466,4153100/500/1000
3.513.2.4.3.0075.0.000660,7512,179,7178100/500/1000
3.513.2.4.3.0075.0.000770,7513,192,9206100/500/1000
3.513.2.4.3.0075.0.000880,7513,6106,2228100/500/1000
3.513.2.4.3.0075.0.000990,7514,4119,5255100/500/1000
3.513.2.4.3.0075.0.0010100,7515132,7278100/500/1000


Part NumberPair CountConductor Diameter (mm²)Approx. Cable Diameter (mm)Copper Weight (kg/km)Approx. Weight (kg/km)Packing Lengths (m)
3.513.2.4.3.0100.0.0001116,116,646100/500/1000
3.513.2.4.3.0100.0.0002218,133,279100/500/1000
3.513.2.4.3.0100.0.0003319,449,8110100/500/1000
3.513.2.4.3.0100.0.00044111,566,4148100/500/1000
3.513.2.4.3.0100.0.0005511283173100/500/1000
3.513.2.4.3.0100.0.00066112,799,6203100/500/1000
3.513.2.4.3.0100.0.00077113,8116,2235100/500/1000
3.513.2.4.3.0100.0.00088114,4132,7261100/500/1000
3.513.2.4.3.0100.0.00099115,2149,3292100/500/1000
3.513.2.4.3.0100.0.001010115,9165,9319100/500/1000


Part NumberPair CountConductor Diameter (mm²)Approx. Cable Diameter (mm)Copper Weight (kg/km)Approx. Weight (kg/km)Packing Lengths (m)
3.513.2.4.3.0150.0.000111,56,825,961100/500/1000
3.513.2.4.3.0150.0.000221,59,151,7106100/500/1000
3.513.2.4.3.0150.0.000331,510,577,6148100/500/1000
3.513.2.4.3.0150.0.000441,512,9103,4198100/500/1000
3.513.2.4.3.0150.0.000551,513,4129,3234100/500/1000
3.513.2.4.3.0150.0.000661,514,3155,1275100/500/1000
3.513.2.4.3.0150.0.000771,515,6181319100/500/1000
3.513.2.4.3.0150.0.000881,516,2206,8355100/500/1000
3.513.2.4.3.0150.0.000991,517,1232,6398100/500/1000
3.513.2.4.3.0150.0.0010101,517,9258,5435100/500/1000


Part NumberPair CountConductor Diameter (mm²)Approx. Cable Diameter (mm)Copper Weight (kg/km)Approx. Weight (kg/km)Packing Lengths (m)
3.513.2.4.3.0250.0.000112,5843,187100/500/1000
3.513.2.4.3.0250.0.000222,510,986,2158100/500/1000
3.513.2.4.3.0250.0.000332,512,8129,3226100/500/1000
3.513.2.4.3.0250.0.000442,515,7172,3303100/500/1000
3.513.2.4.3.0250.0.000552,516,4215,4361100/500/1000
Bending RadiusTemperature Range
Operating
10xD mm-40°C~+70°C
Notes:
Reference Standard: DIN VDE 0812