• At machine and equipment that are required to continue its function during a fire |
• At ventilation systems which are connected to fire alarm system |
• At emergency power supplies |
• In places where human life, valuable materials and equipments need to be protected |
1 - Conductor | : | Class 1/Class 2 electrolytic copper (IEC 60228, DIN VDE 0295, EN 60228) |
2 - Wrapping | : | Each conductor wrapped with mica tape |
3 - Insulation | : | Wrapped conductors insulated with VDE 0266 HXI1 Cross-linked HFFR compound |
4 - Stranding | : | Insulations are stranded into layers |
5 - Filler | : | Halogen-free compound |
6 - Outer Jacket | : | UV resistant, halogen-free outer jacket |
Cross Section | Conductor Resistance Ω/km (20 °C) | Operating Voltage V DC | Test Voltage V DC (1 minute) |
---|---|---|---|
1.50 mm² | 12.1 | 600/1000 | 4000 |
2.50 mm² | 7.4 | 600/1000 | 4000 |
4.00 mm² | 4.6 | 600/1000 | 4000 |
6.00 mm² | 3.1 | 600/1000 | 4000 |
10.00 mm² | 1.8 | 600/1000 | 4000 |
16.00 mm² | 1.2 | 600/1000 | 4000 |
25.00 mm² | 0.7 | 600/1000 | 4000 |
35.00 mm² | 0.5 | 600/1000 | 4000 |
Smoke Density Test | Corrosive Gas Test | Halogen-free Test | Flame Retardancy Test | Flame Propagation Test |
---|---|---|---|---|
IEC 61034-2 VDE 0482-1034-2 BS EN 61034-2 | IEC 60754-2 VDE 0482-267-2-3 BS EN 50267-2-3 | IEC 60754-1 VDE 0482-267-2-1 EN 50267-2-1 BS EN 50267-2-1 | IEC 60332-1-2 VDE 0482-332-1-2 EN 60332-1-2 | IEC 60332-3-24 VDE 0482-332-3-24 BS EN 60332-3-24 |
Circuit Integrity Test (FE180) |
---|
IEC 60331-23 |
Part Number | Conductor Count | Conductor Cross-Section (mm²) | Approx. Cable Diameter (mm) | Copper Weight (kg/km) | Approx. Cable Weight (kg/km) | Packing Lengths (m) |
---|---|---|---|---|---|---|
3.670.01.mt.cX14.0.3.3|0.S1L.03 | 3 | 1.50 | 10.3 | 39.5 | 153 | 500/1000 |
3.670.01.mt.cX14.0.3.3|0.S2L.04 | 4 | 1.50 | 12.6 | 58.0 | 234 | 500/1000 |
3.670.01.mt.cX14.0.0.3|0.S2L.07 | 7 | 1.50 | 14.1 | 96.2 | 310 | 500/1000 |
Part Number | Conductor Count | Conductor Cross-Section (mm²) | Approx. Cable Diameter (mm) | Copper Weight (kg/km) | Approx. Cable Weight (kg/km) | Packing Lengths (m) |
---|---|---|---|---|---|---|
3.670.01.mt.cX14.0.3.3|0.S1N.03 | 3 | 2.50 | 11.2 | 66.5 | 197 | 500/1000 |
3.670.01.mt.cX14.0.3.3|0.S1N.04 | 4 | 2.50 | 12.1 | 92.7 | 237 | 500/1000 |
3.670.01.mt.cX14.0.3.3|0.S1N.05 | 5 | 2.50 | 13.1 | 110.9 | 280 | 500/1000 |
3.670.01.mt.cX14.0.0.3|0.S1N.07 | 7 | 2.50 | 14.2 | 162.3 | 343 | 500/1000 |
3.670.01.mt.cX14.0.0.3|0.S1N.19 | 19 | 2.50 | 21.4 | 440.5 | 795 | 500/1000 |
Part Number | Conductor Count | Conductor Cross-Section (mm²) | Approx. Cable Diameter (mm) | Copper Weight (kg/km) | Approx. Cable Weight (kg/km) | Packing Lengths (m) |
---|---|---|---|---|---|---|
3.670.01.mt.cX14.0.3.3|0.S1O.03 | 3 | 4.00 | 12.0 | 108.2 | 252 | 500/1000 |
3.670.01.mt.cX14.0.3.3|0.S1O.05 | 5 | 4.00 | 14.2 | 172.6 | 355 | 500/1000 |
Part Number | Conductor Count | Conductor Cross-Section (mm²) | Approx. Cable Diameter (mm) | Copper Weight (kg/km) | Approx. Cable Weight (kg/km) | Packing Lengths (m) |
---|---|---|---|---|---|---|
3.670.01.mt.cX14.0.3.3|0.S1P.03 | 3 | 6.00 | 13.1 | 159.1 | 324 | 500/1000 |
3.670.01.mt.cX14.0.3.3|0.S1P.04 | 4 | 6.00 | 14.2 | 221.7 | 402 | 500/1000 |
3.670.01.mt.cX14.0.3.3|0.S1P.05 | 5 | 6.00 | 16.7 | 277.1 | 553 | 500/1000 |
Part Number | Conductor Count | Conductor Cross-Section (mm²) | Approx. Cable Diameter (mm) | Copper Weight (kg/km) | Approx. Cable Weight (kg/km) | Packing Lengths (m) |
---|---|---|---|---|---|---|
3.670.01.mt.cX14.0.3.3|0.S1Q.03 | 3 | 10.00 | 14.8 | 270.0 | 467 | 500/1000 |
3.670.01.mt.cX14.0.3.3|0.S1Q.04 | 4 | 10.00 | 17.3 | 375.2 | 656 | 500/1000 |
3.670.01.mt.cX14.0.3.3|0.S1Q.05 | 5 | 10.00 | 18.8 | 470.0 | 798 | 500/1000 |
Part Number | Conductor Count | Conductor Cross-Section (mm²) | Approx. Cable Diameter (mm) | Copper Weight (kg/km) | Approx. Cable Weight (kg/km) | Packing Lengths (m) |
---|---|---|---|---|---|---|
3.670.01.mt.cX14.0.3.3|0.S2R.03 | 3 | 16.00 | 19.4 | 468.2 | 809 | 500/1000 |
3.670.01.mt.cX14.0.3.3|0.S2R.04 | 4 | 16.00 | 21.1 | 624.2 | 991 | 500/1000 |
3.670.01.mt.cX14.0.3.3|0.S2R.05 | 5 | 16.00 | 23.0 | 780.3 | 1210 | 500/1000 |
Part Number | Conductor Count | Conductor Cross-Section (mm²) | Approx. Cable Diameter (mm) | Copper Weight (kg/km) | Approx. Cable Weight (kg/km) | Packing Lengths (m) |
---|---|---|---|---|---|---|
3.670.01.mt.cX14.0.3.3|0.S2S.04 | 4 | 25.00 | 25.2 | 991.6 | 1480 | 500/1000 |
Part Number | Conductor Count | Conductor Cross-Section (mm²) | Approx. Cable Diameter (mm) | Copper Weight (kg/km) | Approx. Cable Weight (kg/km) | Packing Lengths (m) |
---|---|---|---|---|---|---|
3.670.01.mt.cX14.0.3.3|0.S2T.04 | 4 | 35.00 | 28.3 | 1388.0 | 1947 | 500/1000 |
Bending Radius | Temperature Range Operating |
---|---|
8xD mm | -20°C ~ +90°C |