N2XH-J 0.6-1kV

• In energy networks, hotels, schools, tunnels, high constructions, hospitals, power plants, data processing centers, business centers where there is a risk of fire
• In places where human life, valuable materials and equipments need to be protected
1 - Conductor:Class 1/Class 2 electrolytic copper (IEC 60228, DIN VDE 0295, EN 60228)
2 - Insulation:XLPE (BS EN 50290-2, VDE 0207 YI1)
3 - Stranding:Insulations are stranded into layers
4 - Filler:Halogen-free compound
5 - Outer Jacket:UV resistant, halogen-free outer jacket
Cross
Section
Conductor Resistance
Ω/km
(20 °C)
Operating Voltage
V DC
Test Voltage
V DC
(1 minute)
1.50 mm²12.1600/10004000
2.50 mm²7.4600/10004000
4.00 mm²4.6600/10004000
6.00 mm²3.1600/10004000
10.00 mm²1.8600/10004000
16.00 mm²1.2600/10004000
25.00 mm²0.7600/10004000
35.00 mm²0.5600/10004000
Smoke Density TestCorrosive Gas TestHalogen-free TestFlame Retardancy TestFlame Propagation Test
IEC 61034-2
VDE 0482-1034-2
BS EN 61034-2
IEC 60754-2
VDE 0482-267-2-3
BS EN 50267-2-3
IEC 60754-1
VDE 0482-267-2-1
EN 50267-2-1
BS EN 50267-2-1
IEC 60332-1-2
VDE 0482-332-1-2
EN 60332-1-2
IEC 60332-3-24
VDE 0482-332-3-24
BS EN 60332-3-24
Part NumberConductor
Count
Conductor
Cross-Section
(mm²)
Approx.
Cable
Diameter
(mm)
Copper
Weight
(kg/km)
Approx.
Cable
Weight
(kg/km)
Packing
Lengths
(m)
3.670.01.cX13.0.0.3|0.S1L.0221.509.227.5129500/1000
3.670.01.cX14.0.0.3|0.S1L.0331.5010.441.3168500/1000
3.670.01.cX14.0.0.3|0.S1L.0441.5011.155.0193500/1000


Part NumberConductor
Count
Conductor
Cross-Section
(mm²)
Approx.
Cable
Diameter
(mm)
Copper
Weight
(kg/km)
Approx.
Cable
Weight
(kg/km)
Packing
Lengths
(m)
3.670.01.cX14.0.0.3|0.S1N.0222.5010.846.4185500/1000
3.670.01.cX14.0.0.3|0.S1N.0332.5011.369.6214500/1000
3.670.01.cX14.0.0.3|0.S1N.0552.5013.0115.9293500/1000
3.670.01.cX14.0.0.3|0.S1N.0662.5013.9139.1336500/1000


Part NumberConductor
Count
Conductor
Cross-Section
(mm²)
Approx.
Cable
Diameter
(mm)
Copper
Weight
(kg/km)
Approx.
Cable
Weight
(kg/km)
Packing
Lengths
(m)
3.670.01.cX14.0.0.3|0.S1O.0334.0012.2108.2270500/1000
3.670.01.cX14.0.0.3|0.S1O.0554.0014.2180.3383500/1000


Part NumberConductor
Count
Conductor
Cross-Section
(mm²)
Approx.
Cable
Diameter
(mm)
Copper
Weight
(kg/km)
Approx.
Cable
Weight
(kg/km)
Packing
Lengths
(m)
3.670.01.cX14.0.0.3|0.S1P.0336.0013.3166.3351500/1000
3.670.01.cX13.0.0.3|0.S1P.0446.0014.3221.7422500/1000
3.670.01.cX14.0.0.3|0.S1P.0446.0014.3221.7422500/1000
3.670.01.cX14.0.0.3|0.S1P.0556.0015.5277.1505500/1000
3.670.01.cX14.0.0.3|0.S1P.0556.0015.5277.1504500/1000


Part NumberConductor
Count
Conductor
Cross-Section
(mm²)
Approx.
Cable
Diameter
(mm)
Copper
Weight
(kg/km)
Approx.
Cable
Weight
(kg/km)
Packing
Lengths
(m)
3.670.01.cX14.0.0.3|0.S1Q.03310.0015.1281.5505500/1000
3.670.01.cX14.0.0.3|0.S1Q.04410.0016.4375.3621500/1000
3.670.01.cX14.0.0.3|0.S1Q.05510.0017.8469.1749500/1000


Part NumberConductor
Count
Conductor
Cross-Section
(mm²)
Approx.
Cable
Diameter
(mm)
Copper
Weight
(kg/km)
Approx.
Cable
Weight
(kg/km)
Packing
Lengths
(m)
3.670.01.cX13.0.0.3|0.S2R.02216.0016.7312.1578500/1000
3.670.01.cX13.0.0.3|0.S2R.04416.0019.3624.3899500/1000
3.670.01.cX14.0.0.3|0.S2R.05516.0022.0780.31142500/1000


Part NumberConductor
Count
Conductor
Cross-Section
(mm²)
Approx.
Cable
Diameter
(mm)
Copper
Weight
(kg/km)
Approx.
Cable
Weight
(kg/km)
Packing
Lengths
(m)
3.670.01.cX14.0.0.3|0.S2S.05525.0026.61239.51725500/1000
Bending RadiusTemperature Range
Operating
8xD mm-20°C ~ +90°C