EIB-2Y(St)H

• In places where human life, valuable materials and equipments need to be protected.
• In crowded indoor environments.
• At instrumentation and control engineering.
• At industrial electronics.
• Computer and office devices.
• Indoor communication systems.
• Indoor sound systems.
• Security and fire alarm systems.
1 - Conductor:Class 1 electrolytic solid copper (IEC 60228, DIN VDE 0295, EN 60228)
2 - Insulation:Polyethylene compound (VDE 0815, EN 50290-2-26)
3 - Stranding:Two pairs are stranded into a star-quad, above two pairs are stranded together in layers
4 - Wrapping:Polyester tape
5 - Screen:Tinned copper earthing wire, Al/PET tape
6 - Outer Jacket:UV resistant halogen-free outer jacket. RAL 6018 (Green)
Conductor
Diameter
Conductor Resistance
Ω/km
(20 °C)
Insulation
Resistance
(@500V DC)
MΩ/km
Mutual Capacitance

nF/km
Operating
Voltage

V DC
Test Voltage

(@ 1 minute)
V DC
0.60 mm130.05000100300800
0.80 mm73.25000100300800
1.00 mm44.650001003001000
1.50 mm²24.650001003001000
2.50 mm²15.150001003001000
Smoke Density TestCorrosive Gas TestHalogen-free TestFlame Propagation TestFlame Retardancy Test
IEC 61034-2,
VDE 0482-1034-2,
BS EN 61034-2
IEC 60754-2,
VDE 0482-267-2-3,
BS EN 50267-2-3
IEC 60754-1,
VDE 0482-267-2-1,
BS EN 50267-2-1
IEC 60332-3-24,
VDE 0482-332-3-24,
EN 60332-2-24
IEC 60332-1-2,
VDE 0482-332-1-2,
BS EN 60332-1-2
Bending RadiusTemperature Range
Operating
10xD mm-30°C ~ +70°C