N2XRH-J 0.6/1kV FE180 Fire Resistant Cable

Product Code: N2XRH-J 0.6/1kV FE180

1 – Conductor:Class 1 solid or Class 2/Class 5 stranded electrolytic copper conductor (IEC 60228, DIN VDE 0295, EN 60228).
2 – Wrapping:Each conductor wrapped with mica tape.
3 – Insulation:Wrapped conductors insulated with XLPE (BS EN 50290-2, VDE 0207 YI1, HD 308 S2).
4 – Stranding:Insulations are stranded into layers.
5 – Filling:Halogen-free compund.
6 – Armour:Galvanized steel wire armor, polyester tape.
7 – Outer Jacket:UV resistant halogen-free outer jacket. RAL 2008 (Orange)
Cross
Section
Conductor Resistance
Ω/km
(20 °C)
Operating
Voltage

V DC
Test Voltage

(@ 1 minute)
V
1.50 mm²12.1600/10004000
2.50 mm²7.41600/10004000
4.00 mm²4.61600/10004000
6.00 mm²3.08600/10004000
10.00 mm²1.83600/10004000
16.00 mm²1.15600/10004000
25.00 mm²0.727600/10004000
35.00 mm²0.524600/10004000
Smoke Density TestCorrosive Gas TestHalogen-free TestFlame Propagation TestFlame Retardancy Test
IEC 61034-2,
VDE 0482-1034-2,
BS EN 61034-2
IEC 60754-2,
VDE 0482-267-2-3,
BS EN 50267-2-3
IEC 60754-1,
VDE 0482-267-2-1,
BS EN 50267-2-1
IEC 60332-3-24,
VDE 0482-332-3-24,
EN 60332-2-24
IEC 60332-1-2,
VDE 0482-332-1-2,
BS EN 60332-1-2
Circuit Integrity Test
(FE180)
IEC 60331-21
Bending RadiusTemperature Range
Operating
10xD mm-40°C ~ +90°C