RE-2Y(St)YSWBY-PiMF/TiMF Instrumentation Cable

Product Code: RE-2Y(St)YSWBY-PiMF/TiMF

1 – Conductor:Stranded electrolytic copper conductor (Class 2) (IEC 60228, EN 60228, DIN VDE 0295)
2 – Insulation:Polyethylene (BS EN 50290-2, VDE 0207 YI1), Black, White, Red; Number coded (BS 5308-2)
3 – Individual Stranding:Insulations stranding into pairs or triads
4 – Individual Wrapping:Polyester tape
5 – Individual Screen:Tinned copper earthing wire, Al/PET tape
6 – Overall Stranding:Screened pairs or triads are stranded in layers.
7 – Overall Wrapping:Polyester tape
8 – Overall Screen:Tinned copper earthing wire, Al/PET tape
9 – Inner Jacket:PVC inner jacket. RAL 9005 (Black)
10 – Armor:Galvanized steel wire braiding
11 – Outer Jacket:UV resistant PVC outer jacket. RAL 9005 (Black)
Conductor
Diameter
Conductor Resistance
Ω/km
(20 °C)
Insulation
Resistance
(@500V DC)
MΩ/km
Mutual Capacitance

nF/km
Operating
Voltage

V DC
Test Voltage

(@ 1 minute)
V DC
0.50 mm²36.05000160300/5002000
0.75 mm²24.55000160300/5002000
1.00 mm²18.15000170300/5002000
1.50 mm²12.15000170300/5002000
2.50 mm²7.415000170300/5002000
Manufacturing ReferanceFlame Retardancy Test
EN 50288-7
or
IEC 60502-1
IEC 60332-1-2
Bending RadiusTemperature Range
Operating
7.5xD mm-30°C ~ +70°C