| 1 – Conductor | : | Electrolytic solid copper conductor |
| 2 – Insulation | : | Solid polyethylene insulation |
| 3 – Stranding | : | Insulations are stranded into pairs |
| 4 – Seperator | : | Pairs are stranded together with star shaped separator |
| 5 – Outer Jacket | : | UV resistant halogen-free outer jacket |
| Conductor Diameter | Conductor Resistance Ω/km (20 °C) | Insulation Resistance (@500V DC) MΩ/km | Mutual Capacitance nF/km | Operating Voltage V DC | Test Voltage (@ 1 minute) V DC |
|---|---|---|---|---|---|
| 0.50 mm² | 36.0 | Min. 1000 | Max. 250 | 300 | 2000 |
| 0.75 mm² | 24.5 | Min. 1000 | Max. 250 | 300 | 2000 |
| 1.00 mm² | 18.1 | Min. 1000 | Max. 250 | 300 | 2000 |
| 1.50 mm² | 12.1 | Min. 1000 | Max. 250 | 300 | 2000 |
| 2.50 mm² | 7.41 | Min. 1000 | Max. 250 | 300 | 2000 |
| Smoke Density Test | Corrosive Gas Test | Halogen-free Test | Flame Propagation Test | Flame Retardancy Test | Fire Resistance Test (FE180) |
|---|---|---|---|---|---|
| IEC 61034-2, VDE 0482-1034-2, BS EN 61034-2 | IEC 60754-2, VDE 0482-267-2-3, BS EN 50267-2-3 | IEC 60754-1, VDE 0482-267-2-1, BS EN 50267-2-1 | IEC 60332-3-24, VDE 0482-332-3-24, EN 60332-2-24 | IEC 60332-1-2, VDE 0482-332-1-2, BS EN 60332-1-2 | IEC 60331-21 |
| Bending Radius | Temperature Range Operating |
|---|---|
| 10xD mm | -30°C ~ +90°C |