| 1 – Conductor | : | Class 1 electrolytic solid copper (IEC 60228, DIN VDE 0295, EN 60228) |
| 2 – Insulation | : | Cross-linked polymer compound in ceramic form (VDE 0815) |
| 3 – Stranding | : | Insulations are stranded into pairs, four pairs are stranded together into groups, groups are stranded in layers. |
| 4 – Wrapping | : | Polyester tape, glass yarn tape |
| 5 – Screen | : | Tinned copper earthing wire, Al/PET tape |
| 6 – Outer Jacket | : | UV resistant halogen-free outer jacket. RAL 2008 (Orange) |
| Conductor Diameter | Conductor Resistance Ω/km (20 °C) | Insulation Resistance (@500V DC) MΩ/km | Mutual Capacitance nF/km | Operating Voltage V DC | Test Voltage (@ 1 minute) V DC |
|---|---|---|---|---|---|
| 0.60 mm | 130.0 | 100 | 100 | 300 | 1000 |
| 0.80 mm | 73.2 | 100 | 100 | 300 | 1000 |
| 1.00 mm | 44.6 | 100 | 100 | 300 | 1000 |
| 1.50 mm² | 24.6 | 100 | 100 | 300 | 1000 |
| 2.50 mm² | 15.1 | 100 | 100 | 300 | 1000 |
| Smoke Density Test | Corrosive Gas Test | Halogen-free Test | Flame Propagation Test | Flame Retardancy Test |
|---|---|---|---|---|
| IEC 61034-2, VDE 0482-1034-2, BS EN 61034-2 | IEC 60754-2, VDE 0482-267-2-3, BS EN 50267-2-3 | IEC 60754-1, VDE 0482-267-2-1, BS EN 50267-2-1 | IEC 60332-3-24, VDE 0482-332-3-24, EN 60332-2-24 | IEC 60332-1-2, VDE 0482-332-1-2, BS EN 60332-1-2 |
| Circuit Integrity Test (FE180) | Circuit Integrity with Shock Test (PH120) |
|---|---|
| IEC 60331-21 | EN 50200, VDE 0482-200, BS EN 50200 |
| Part Number | Pair Count | Conductor Diameter (mm) | Approx. Cable Diameter (mm) | Copper Weight (kg/km) | Approx. Weight (kg/km) | Packing Lengths (m) |
|---|---|---|---|---|---|---|
| 3.650.1.4.3.0060.0.0001 | 1 | 0,6 | 4,6 | 8,1 | 27 | 100/500/1000 |
| 3.650.1.4.3.0060.0.0002 | 2 | 0,6 | 5,3 | 13,4 | 39 | 100/500/1000 |
| 3.650.1.4.3.0060.0.0003 | 3 | 0,6 | 6,7 | 18,8 | 55 | 100/500/1000 |
| 3.650.1.4.3.0060.0.0004 | 4 | 0,6 | 7,9 | 24,2 | 69 | 100/500/1000 |
| 3.650.1.4.3.0060.0.0005 | 5 | 0,6 | 8,3 | 29,5 | 81 | 100/500/1000 |
| 3.650.1.4.3.0060.0.0006 | 6 | 0,6 | 10 | 34,9 | 98 | 100/500/1000 |
| 3.650.1.4.3.0060.0.0008 | 8 | 0,6 | 10,3 | 45,6 | 116 | 100/500/1000 |
| 3.650.1.4.3.0060.0.0010 | 10 | 0,6 | 10,7 | 56,3 | 136 | 100/500/1000 |
| Part Number | Pair Count | Conductor Diameter (mm) | Approx. Cable Diameter (mm) | Copper Weight (kg/km) | Approx. Weight (kg/km) | Packing Lengths (m) |
|---|---|---|---|---|---|---|
| 3.650.1.4.3.0080.0.0001 | 1 | 0,8 | 5,4 | 14,3 | 38 | 100/500/1000 |
| 3.650.1.4.3.0080.0.0002 | 2 | 0,8 | 6,2 | 23,8 | 54 | 100/500/1000 |
| 3.650.1.4.3.0080.0.0003 | 3 | 0,8 | 7,9 | 33,4 | 80 | 100/500/1000 |
| 3.650.1.4.3.0080.0.0004 | 4 | 0,8 | 9,5 | 42,9 | 103 | 100/500/1000 |
| 3.650.1.4.3.0080.0.0005 | 5 | 0,8 | 9,8 | 52,4 | 119 | 100/500/1000 |
| 3.650.1.4.3.0080.0.0006 | 6 | 0,8 | 11,9 | 62 | 144 | 100/500/1000 |
| 3.650.1.4.3.0080.0.0008 | 8 | 0,8 | 12,3 | 81 | 178 | 100/500/1000 |
| 3.650.1.4.3.0080.0.0010 | 10 | 0,8 | 12,8 | 100,1 | 208 | 100/500/1000 |
| Part Number | Pair Count | Conductor Diameter (mm) | Approx. Cable Diameter (mm) | Copper Weight (kg/km) | Approx. Weight (kg/km) | Packing Lengths (m) |
|---|---|---|---|---|---|---|
| 3.650.1.4.3.0100.0.0001 | 1 | 1 | 5,7 | 19,6 | 48 | 100/500/1000 |
| 3.650.1.4.3.0100.0.0002 | 2 | 1 | 7 | 34,4 | 71 | 100/500/1000 |
| 3.650.1.4.3.0100.0.0003 | 3 | 1 | 9 | 49,5 | 105 | 100/500/1000 |
| 3.650.1.4.3.0100.0.0004 | 4 | 1 | 10,8 | 64,3 | 137 | 100/500/1000 |
| 3.650.1.4.3.0100.0.0005 | 5 | 1 | 11,2 | 79,2 | 160 | 100/500/1000 |
| 3.650.1.4.3.0100.0.0006 | 6 | 1 | 13,8 | 94,1 | 197 | 100/500/1000 |
| 3.650.1.4.3.0100.0.0008 | 8 | 1 | 14,2 | 123,9 | 240 | 100/500/1000 |
| 3.650.1.4.3.0100.0.0010 | 10 | 1 | 14,7 | 153,6 | 286 | 100/500/1000 |
| Part Number | Pair Count | Conductor Diameter (mm) | Approx. Cable Diameter (mm) | Copper Weight (kg/km) | Approx. Weight (kg/km) | Packing Lengths (m) |
|---|---|---|---|---|---|---|
| 3.650.1.4.3.0150.0.0001 | 1 | 1,5 | 7 | 32,2 | 65 | 100/500/1000 |
| 3.650.1.4.3.0150.0.0002 | 2 | 1,5 | 8,1 | 59,6 | 107 | 100/500/1000 |
| 3.650.1.4.3.0150.0.0003 | 3 | 1,5 | 10,5 | 87,4 | 160 | 100/500/1000 |
| 3.650.1.4.3.0150.0.0004 | 4 | 1,5 | 12,7 | 114,9 | 209 | 100/500/1000 |
| 3.650.1.4.3.0150.0.0005 | 5 | 1,5 | 13,3 | 142,4 | 247 | 100/500/1000 |
| 3.650.1.4.3.0150.0.0006 | 6 | 1,5 | 16,4 | 170 | 306 | 100/500/1000 |
| 3.650.1.4.3.0150.0.0008 | 8 | 1,5 | 17,1 | 225 | 387 | 100/500/1000 |
| 3.650.1.4.3.0150.0.0010 | 10 | 1,5 | 17,6 | 280 | 459 | 100/500/1000 |
| Part Number | Pair Count | Conductor Diameter (mm) | Approx. Cable Diameter (mm) | Copper Weight (kg/km) | Approx. Weight (kg/km) | Packing Lengths (m) |
|---|---|---|---|---|---|---|
| 3.650.1.4.3.0250.0.0001 | 1 | 2,5 | 8 | 49,7 | 95 | 100/500/1000 |
| 3.650.1.4.3.0250.0.0002 | 2 | 2,5 | 9,2 | 94,5 | 156 | 100/500/1000 |
| 3.650.1.4.3.0250.0.0003 | 3 | 2,5 | 12,1 | 140 | 227 | 100/500/1000 |
| 3.650.1.4.3.0250.0.0004 | 4 | 2,5 | 14,7 | 185 | 298 | 100/500/1000 |
| 3.650.1.4.3.0250.0.0005 | 5 | 2,5 | 15,4 | 230,1 | 360 | 100/500/1000 |
| 3.650.1.4.3.0250.0.0006 | 6 | 2,5 | 19,1 | 275,1 | 439 | 100/500/1000 |
| 3.650.1.4.3.0250.0.0008 | 8 | 2,5 | 19,9 | 365,2 | 560 | 100/500/1000 |
| 3.650.1.4.3.0250.0.0010 | 10 | 2,5 | 20,5 | 455,3 | 672 | 100/500/1000 |
| Bending Radius | Temperature Range Operating |
|---|---|
| 10xD mm | -40°C ~ +70°C |
JE-H(St)H Bd FE180 PH120 Fire-Resistant Cable for Critical Systems
ETK Kablo’s JE-H(St)H Bd FE180 PH120 Fire-Resistant Cable is a high-performance halogen-free signal cable engineered to maintain circuit integrity and signal reliability under extreme fire conditions. It ensures continuous communication in life-safety systems, emergency networks, and fire detection applications.
Fire Protection and Circuit Integrity
With certified fire endurance ratings of FE180 and PH120, this cable provides up to 180 minutes of cable integrity and 120 minutes of circuit continuity during fire exposure. It supports fire alarm, emergency lighting, building management, and communication systems that must remain operational throughout critical events.
Halogen-Free and Flame-Retardant Design
The LSZH (Low Smoke Zero Halogen) outer sheath ensures minimal toxic smoke and corrosive gas emission, improving personal safety and property protection. Its halogen-free construction makes it suitable for use in hospitals, airports, tunnels, and commercial buildings where fire safety standards are mandatory.
Shielding and Signal Stability
The aluminum polyester foil screen (St) provides effective electromagnetic interference (EMI) protection, enabling stable and interference-free signal transmission in sensitive low-voltage control networks. This makes the cable ideal for structured communication cabling where both safety and data integrity are essential.
Applications and Compliance
JE-H(St)H Bd FE180 PH120 is suitable for fixed installations in public, commercial, and industrial facilities where fire performance and low smoke emission are critical. It complies with IEC 60331, EN 50200, and IEC 60332-3 standards, guaranteeing fire resistance, flame retardancy, and CPR compliance for modern structured cabling networks.
Why Choose ETK Kablo’s JE-H(St)H Bd FE180 PH120?
Choose ETK Kablo’s JE-H(St)H Bd FE180 PH120 — the halogen-free, shielded fire-resistant cable that ensures secure signal transmission, reliable fire protection, and long-term safety in mission-critical installations.
Frequently Asked Questions about JE-H(St)H Bd FE180 PH120 Fire-Resistant Cable
What is fire-resistant cable?
A fire-resistant cable is engineered to maintain circuit integrity during fire conditions. ETK Kablo’s JE-H(St)H Bd FE180 PH120 withstands up to 180 minutes of cable integrity (FE180) and 120 minutes of circuit operation (PH120), ensuring continuous signal transmission in life-safety and communication systems during a fire.
What is the difference between FR and FRLS cable?
FR (Flame-Retardant) cables resist the spread of flame, while FRLS (Flame-Retardant Low Smoke) versions emit less smoke. In contrast, JE-H(St)H Bd FE180 PH120 is a fire-resistant LSZH (halogen-free) cable that continues operating during a fire, combining FE180/PH120 endurance with zero halogen emissions for superior personal safety.
What is a fire-resistant cable as per IEC 60331?
According to IEC 60331, a fire-resistant cable must maintain electrical circuit integrity under flame for a specified duration. The JE-H(St)H Bd FE180 PH120 meets this requirement by keeping signals operational for 180 minutes in fire tests, exceeding standard IEC 60331-23 and EN 50200 PH120 classifications.
What is the difference between FR and FRT cable?
FR cables prevent flame spread but may lose function, while FRT (Fire-Resistant Type) cables continue transmitting during a fire. The JE-H(St)H Bd FE180 PH120 belongs to the FRT category, maintaining both insulation integrity and signal continuity in critical alarm or emergency communication circuits.
What is another name for fire-resistant cable?
Fire-resistant cables are also known as circuit integrity cables or fire-survival cables. ETK Kablo’s JE-H(St)H Bd FE180 PH120 is one such fire-survival cable, specially designed for emergency lighting, evacuation systems, and fire detection networks that must operate under high-temperature exposure.
Which is better — fire-resistant or flame-retardant?
Fire-resistant cables like JE-H(St)H Bd FE180 PH120 are superior when circuit continuity is essential, as they keep transmitting during a fire. Flame-retardant cables simply resist ignition and limit flame spread. For critical infrastructure such as hospitals, tunnels, airports, and control centers, fire-resistant cables are the preferred and safer choice.