(N)HXH-J 0.6/1kV FE180 E90 Fire Resistant Cable

Product Code: (N)HXH-J 0.6/1kV FE180 E90

1 – Conductor:Class 1 solid or Class 2 stranded electrolytic copper conductor (IEC 60228, DIN VDE 0295, EN 60228).
2 – Insulation:Cross-linked polymer compound in ceramic form (VDE 0815).
3 – Stranding:Insulations are stranded into layers.
4 – Filling:Halogen-free compund.
5 – Outer Jacket:UV resistant halogen-free outer jacket. RAL 2008 (Orange)
Cross
Section
Conductor Resistance
Ω/km
(20 °C)
Operating
Voltage

V DC
Test Voltage

(@ 1 minute)
V
0.50 mm²36.0600/10004000
0.75 mm²24.5600/10004000
1.00 mm²18.1600/10004000
1.50 mm²12.1600/10004000
2.50 mm²7.41600/10004000
4.00 mm²4.61600/10004000
6.00 mm²3.08600/10004000
10.00 mm²1.83600/10004000
16.00 mm²1.15600/10004000
25.00 mm²0.727600/10004000
35.00 mm²0.524600/10004000
Smoke Density TestCorrosive Gas TestHalogen-free TestFlame Propagation TestFlame Retardancy Test
IEC 61034-2,
VDE 0482-1034-2,
BS EN 61034-2
IEC 60754-2,
VDE 0482-267-2-3,
BS EN 50267-2-3
IEC 60754-1,
VDE 0482-267-2-1,
BS EN 50267-2-1
IEC 60332-3-24,
VDE 0482-332-3-24,
EN 60332-2-24
IEC 60332-1-2,
VDE 0482-332-1-2,
BS EN 60332-1-2
Circuit Integrity Test
(FE180)
Cable System Circuit Integrity Test
(E30 / E60 / E90)
IEC 60331-21DIN 4102-12
Bending RadiusTemperature Range
Operating
10xD mm-40°C ~ +90°C

(N)HXH-J FE180 E90 Cable for Emergency Power Circuits

(N)HXH-J FE180 E90 cable is a halogen-free power cable rated at 0.6/1 kV for fixed installations with specified circuit-integrity requirements. It combines copper conductors, cross-linked ceramic-forming insulation, halogen-free filling and an orange outer sheath.

Part of our fire-resistant power cable range, this product serves building and infrastructure projects with specified circuit-integrity requirements. Cable selection and installation must follow the documented fire-performance scope for the required configuration.

What Do FE180 and E90 Mean?

FE180 describes 180-minute cable circuit integrity under the specified fire-test conditions. The product documentation lists IEC 60331-21 as the relevant test reference.

E90 describes 90-minute functional integrity of a tested cable installation system under DIN 4102-12. It applies to the cable together with the approved supports, fixings and installation arrangement. Specifying an E90 cable therefore requires selecting the corresponding installation system as well.

The two durations refer to different tests and should not be added together. Read our FE180, PH120 and E30/E60/E90 guide for a comparison of cable-level and installation-system performance.

Applications for Fire-Resistant Power Wiring

Typical project applications include power supplies for emergency lighting, smoke extraction and other essential building services, subject to the system design and required approvals. Installation contexts include hospitals, hotels, high-rise buildings, tunnels and industrial facilities.

Select the conductor cross-section for the load, voltage drop, protective devices and installation conditions. For an E90 installation, also check the permitted cable sizes, support spacing, fixing method and cable loading in the applicable system documentation.

Selected (N)HXH-J FE180 E90 Cable Sizes

The following configurations appear in the product datasheet. In a size such as 3×1.5 mm², the first number is the conductor count and the second is the cross-sectional area of each conductor.

Cable SizeConductor CountConductor Cross-Section
(N)HXH-J FE180 E90 3×1.5 mm²31.5 mm²
(N)HXH-J FE180 E90 4×1.5 mm²41.5 mm²
(N)HXH-J FE180 E90 5×1.5 mm²51.5 mm²
(N)HXH-J FE180 E90 3×2.5 mm²32.5 mm²
(N)HXH-J FE180 E90 4×2.5 mm²42.5 mm²
(N)HXH-J FE180 E90 5×2.5 mm²52.5 mm²
(N)HXH-J FE180 E90 3×4 mm²34 mm²
(N)HXH-J FE180 E90 5×6 mm²56 mm²

All sizes above have a rated voltage of 0.6/1 kV. The PDF already available on this page lists further configurations, including larger conductor cross-sections up to 35 mm², together with cable diameters, weights and packing lengths.

Halogen-Free Materials and Fire Performance

The halogen-free filling and outer sheath address smoke and halogen requirements alongside the cable’s circuit-integrity specification. These are separate characteristics: low-smoke and halogen-free materials alone do not establish FE180 or E90 performance.

Similarly, a CPR reaction-to-fire classification is separate from circuit integrity during fire. Where the project specifies a particular Euroclass, request the Declaration of Performance for the selected product.

Frequently Asked Questions

Does E90 apply to the cable alone?

No. E90 concerns the tested installation system. The cable, supports and fixings must match the arrangement covered by the applicable documentation.

Is this a screened or armored power cable?

The construction listed for this product has no metallic screen or armor. If the project requires either feature, include it in the enquiry so the appropriate cable design can be selected.

Request a Quotation for (N)HXH-J FE180 E90 Cable

Contact ETK Kablo with the required conductor count, cross-section, total quantity and drum lengths. Include the E90 installation requirements and any CPR classification or approval documents needed for the project.