| 1 – Conductor | : | Stranded electrolytic copper conductor (Class 2) (IEC 60228, EN 60228, DIN VDE 0295) |
| 2 – Insulation | : | XLPE (BS EN 50290-2, VDE 0207 YI1), White; Number coded (BS 5308-2) |
| 3 – Stranding | : | In layers |
| 4 – Wrapping | : | Polyester tape |
| 5 – Screen | : | Tinned copper earthing wire, Al/PET tape |
| 6 – Outer Jacket | : | UV resistant halogen-free outer jacket. RAL 9005 (Black) |
| Conductor Diameter | Conductor Resistance Ω/km (20 °C) | Insulation Resistance (@500V DC) MΩ/km | Mutual Capacitance nF/km | Operating Voltage V DC | Test Voltage (@ 1 minute) V DC |
|---|---|---|---|---|---|
| 0.50 mm² | 36.0 | Min. 1000 | Max. 250 | 300/500 | 2000 |
| 0.75 mm² | 24.5 | Min. 1000 | Max. 250 | 300/500 | 2000 |
| 1.00 mm² | 18.1 | Min. 1000 | Max. 250 | 300/500 | 2000 |
| 1.50 mm² | 12.1 | Min. 1000 | Max. 250 | 300/500 | 2000 |
| 2.50 mm² | 7.41 | Min. 1000 | Max. 250 | 300/500 | 2000 |
| Manufacturing Referance | Smoke Density Test | Corrosive Gas Test | Halogen-free Test | Flame Propagation Test | Flame Retardancy Test |
|---|---|---|---|---|---|
| EN 50288-7, IEC 60502-1 (for 0.6/1kV) | IEC 61034-2, VDE 0482-1034-2, BS EN 61034-2 | IEC 60754-2, VDE 0482-267-2-3, BS EN 50267-2-3 | IEC 60754-1, VDE 0482-267-2-1, BS EN 50267-2-1 | IEC 60332-3-24, VDE 0482-332-3-24, EN 60332-2-24 | IEC 60332-1-2, VDE 0482-332-1-2, BS EN 60332-1-2 |
| Bending Radius | Temperature Range Operating |
|---|---|
| 7.5xD mm | -30°C ~ +90°C |
RE-2X(St)H Cable for Industrial Instrumentation
RE-2X(St)H cable is an overall foil-screened, XLPE-insulated instrumentation cable with a low-smoke, halogen-free outer sheath. ETK Kablo manufactures this cable for measurement, monitoring and process-control circuits where the specification calls for screened signal wiring and an LSZH sheath.
Part of our instrumentation cable range, this unarmored design uses numbered conductors assembled in layers. It provides a distinct option for projects that require multicore wiring rather than a specified twisted-pair or twisted-triad arrangement.
Applications in Measurement and Process Control
RE-2X(St)H can be specified for connections between field instruments, junction boxes and control equipment. Typical project contexts include manufacturing plants, energy facilities and process automation systems. Selection should follow the connected equipment’s requirements for conductor arrangement, resistance, capacitance and screening.
For PLC, DCS or monitoring circuits, match the cable to the signal interface and installation route. Where an equipment specification requires twisted pairs, triads or individually screened circuits, select the corresponding construction from the instrumentation range.
Overall Screening and LSZH Sheath
An Al/PET foil screen surrounds the assembled cores, with a tinned copper drain wire for screen termination. This arrangement helps reduce coupling from external electrical interference when installed and earthed according to the system design.
The black outer sheath is halogen-free and UV resistant. Smoke, halogen and flame-test references are listed in the Standards section above. Where a project requires a specific CPR classification or continued circuit operation during fire, include that requirement in the enquiry so the appropriate cable and supporting documentation can be selected.
RE-2X(St)H Conductor Sizes
The following conductor cross-sections are listed for this product. Specify the required core count together with the cross-section when requesting a quotation.
| Cable Type | Conductor Cross-section |
|---|---|
| RE-2X(St)H | 0.50 mm² |
| RE-2X(St)H | 0.75 mm² |
| RE-2X(St)H | 1.00 mm² |
| RE-2X(St)H | 1.50 mm² |
| RE-2X(St)H | 2.50 mm² |
Refer to the Technical Data section above for electrical values. Core count, overall diameter, delivery length and other order details should be confirmed for the selected configuration.
Related Instrumentation Cable Options
- RE-2X(St)Y instrumentation cable for comparison when selecting the required sheath system.
- RE-2X(St)HSWAH armored instrumentation cable for specifications requiring steel wire armor.
Request a RE-2X(St)H Cable Quotation
Contact ETK Kablo with your required core count, conductor cross-section, total quantity and preferred drum lengths. Include the installation conditions, applicable standards and any fire-performance requirements so our team can confirm the suitable specification and supply details.