| 1 – Conductor | : | Class 1 electrolytic solid copper (IEC 60228, DIN VDE 0295, EN 60228) |
| 2 – Insulation | : | Halogen-free compound (VDE 0815, EN 50290-2-26) |
| 3 – Stranding | : | Two pairs are stranded into a star-quad, above two pairs are stranded together in layers |
| 4 – Wrapping | : | Polyester tape |
| 5 – Screen | : | Tinned copper earthing wire, Al/PET tape |
| 6 – Outer Jacket | : | UV resistant halogen-free outer jacket. RAL 3000 (Red) |
| Conductor Diameter | Conductor Resistance Ω/km (20 °C) | Insulation Resistance (@500V DC) MΩ/km | Mutual Capacitance nF/km | Operating Voltage V DC | Test Voltage (@ 1 minute) V DC |
|---|---|---|---|---|---|
| 0.60 mm | 130.0 | 100 | 100 | 300 | 800 |
| 0.80 mm | 73.2 | 100 | 100 | 300 | 800 |
| 1.00 mm | 44.6 | 100 | 100 | 300 | 1000 |
| 1.50 mm² | 24.6 | 100 | 100 | 300 | 1000 |
| 2.50 mm² | 15.1 | 100 | 100 | 300 | 1000 |
| Smoke Density Test | Corrosive Gas Test | Halogen-free Test | Flame Propagation Test | Flame Retardancy Test |
|---|---|---|---|---|
| IEC 61034-2, VDE 0482-1034-2, BS EN 61034-2 | IEC 60754-2, VDE 0482-267-2-3, BS EN 50267-2-3 | IEC 60754-1, VDE 0482-267-2-1, BS EN 50267-2-1 | IEC 60332-3-24, VDE 0482-332-3-24, EN 60332-2-24 | IEC 60332-1-2, VDE 0482-332-1-2, BS EN 60332-1-2 |
| Part Number | Pair Count | Conductor Diameter (mm) | Cross Section (mm²) | Approx. Cable Diameter (mm) | Copper Weight (kg/km) | Approx. Weight (kg/km) | Packing Lengths (m) |
|---|---|---|---|---|---|---|---|
| 3.644.1.3.3.0060.0.0001 | 1 | 0,6 | – | 4,1 | 7,2 | 22 | 100/500/1000 |
| 3.644.1.3.3.0060.0.0002 | 2 | 0,6 | – | 4,7 | 12,5 | 32 | 100/500/1000 |
| 3.644.1.3.3.0060.0.0003 | 3 | 0,6 | – | 6,1 | 17,8 | 46 | 100/500/1000 |
| 3.644.1.3.3.0060.0.0004 | 4 | 0,6 | – | 7,2 | 23,1 | 58 | 100/500/1000 |
| 3.644.1.3.3.0060.0.0005 | 5 | 0,6 | – | 7,5 | 28,4 | 69 | 100/500/1000 |
| 3.644.1.3.3.0060.0.0006 | 6 | 0,6 | – | 9,1 | 33,7 | 84 | 100/500/1000 |
| 3.644.1.3.3.0060.0.0008 | 8 | 0,6 | – | 9,3 | 44,3 | 101 | 100/500/1000 |
| 3.644.1.3.3.0060.0.0010 | 10 | 0,6 | – | 9,7 | 54,9 | 119 | 100/500/1000 |
| 3.644.1.3.3.0060.0.0012 | 12 | 0,6 | – | 10,4 | 65,6 | 138 | 100/500/1000 |
| 3.644.1.3.3.0060.0.0014 | 14 | 0,6 | – | 11,3 | 76,2 | 162 | 100/500/1000 |
| 3.644.1.3.3.0060.0.0016 | 16 | 0,6 | – | 11,9 | 86,8 | 180 | 100/500/1000 |
| 3.644.1.3.3.0060.0.0020 | 20 | 0,6 | – | 13,3 | 108 | 218 | 100/500/1000 |
| 3.644.1.3.3.0060.0.0024 | 24 | 0,6 | – | 14,3 | 129,2 | 259 | 100/500/1000 |
| 3.644.1.3.3.0060.0.0025 | 25 | 0,6 | – | 14,5 | 134,5 | 268 | 100/500/1000 |
| 3.644.1.3.3.0060.0.0030 | 30 | 0,6 | – | 18,8 | 161,1 | 339 | 100/500/1000 |
| 3.644.1.3.3.0060.0.0040 | 40 | 0,6 | – | 20,8 | 214,1 | 428 | 100/500/1000 |
| 3.644.1.3.3.0060.0.0050 | 50 | 0,6 | – | 23 | 267,2 | 518 | 100/500/1000 |
| 3.644.1.3.3.0060.0.0060 | 60 | 0,6 | – | 25,1 | 320,2 | 620 | 100/500/1000 |
| 3.644.1.3.3.0060.0.0080 | 80 | 0,6 | – | 28,1 | 426,3 | 792 | 100/500/1000 |
| 3.644.1.3.3.0060.0.0100 | 100 | 0,6 | – | 32,1 | 532,4 | 986 | 100/500/1000 |
| Part Number | Pair Count | Conductor Diameter (mm) | Cross Section (mm²) | Approx. Cable Diameter (mm) | Copper Weight (kg/km) | Approx. Weight (kg/km) | Packing Lengths (m) |
|---|---|---|---|---|---|---|---|
| 3.644.1.3.3.0080.0.0001 | 1 | 0,8 | – | 4,6 | 11,3 | 29 | 100/500/1000 |
| 3.644.1.3.3.0080.0.0002 | 2 | 0,8 | – | 5,3 | 20,7 | 44 | 100/500/1000 |
| 3.644.1.3.3.0080.0.0003 | 3 | 0,8 | – | 6,9 | 30,2 | 65 | 100/500/1000 |
| 3.644.1.3.3.0080.0.0004 | 4 | 0,8 | – | 8,1 | 39,6 | 82 | 100/500/1000 |
| 3.644.1.3.3.0080.0.0005 | 5 | 0,8 | – | 8,6 | 49,1 | 98 | 100/500/1000 |
| 3.644.1.3.3.0080.0.0006 | 6 | 0,8 | – | 10,4 | 58,5 | 119 | 100/500/1000 |
| 3.644.1.3.3.0080.0.0008 | 8 | 0,8 | – | 10,7 | 77,3 | 145 | 100/500/1000 |
| 3.644.1.3.3.0080.0.0010 | 10 | 0,8 | – | 11,1 | 96,2 | 173 | 100/500/1000 |
| 3.644.1.3.3.0080.0.0012 | 12 | 0,8 | – | 11,8 | 115,1 | 199 | 100/500/1000 |
| 3.644.1.3.3.0080.0.0014 | 14 | 0,8 | – | 12,8 | 133,9 | 233 | 100/500/1000 |
| 3.644.1.3.3.0080.0.0016 | 16 | 0,8 | – | 13,5 | 152,8 | 261 | 100/500/1000 |
| 3.644.1.3.3.0080.0.0020 | 20 | 0,8 | – | 15,2 | 190,5 | 318 | 100/500/1000 |
| 3.644.1.3.3.0080.0.0024 | 24 | 0,8 | – | 16,2 | 228,3 | 379 | 100/500/1000 |
| 3.644.1.3.3.0080.0.0025 | 25 | 0,8 | – | 16,5 | 237,7 | 391 | 100/500/1000 |
| 3.644.1.3.3.0080.0.0030 | 30 | 0,8 | – | 21,3 | 284,8 | 482 | 100/500/1000 |
| 3.644.1.3.3.0080.0.0040 | 40 | 0,8 | – | 23,8 | 379,2 | 629 | 100/500/1000 |
| 3.644.1.3.3.0080.0.0050 | 50 | 0,8 | – | 26,4 | 473,5 | 766 | 100/500/1000 |
| 3.644.1.3.3.0080.0.0060 | 60 | 0,8 | – | 28,8 | 567,8 | 918 | 100/500/1000 |
| 3.644.1.3.3.0080.0.0080 | 80 | 0,8 | – | 32,3 | 756,4 | 1184 | 100/500/1000 |
| 3.644.1.3.3.0080.0.0100 | 100 | 0,8 | – | 36,8 | 945,1 | 1458 | 100/500/1000 |
| Part Number | Pair Count | Conductor Diameter (mm) | Cross Section (mm²) | Approx. Cable Diameter (mm) | Copper Weight (kg/km) | Approx. Weight (kg/km) | Packing Lengths (m) |
|---|---|---|---|---|---|---|---|
| 3.644.1.3.3.0100.0.0001 | 1 | 1 | – | 5,5 | 19,6 | 42 | 100/500/1000 |
| 3.644.1.3.3.0100.0.0002 | 2 | 1 | – | 6,3 | 34,4 | 65 | 100/500/1000 |
| 3.644.1.3.3.0100.0.0003 | 3 | 1 | – | 8,1 | 49,5 | 92 | 100/500/1000 |
| 3.644.1.3.3.0100.0.0004 | 4 | 1 | – | 9,6 | 64,3 | 117 | 100/500/1000 |
| 3.644.1.3.3.0100.0.0005 | 5 | 1 | – | 10,1 | 79,2 | 140 | 100/500/1000 |
| 3.644.1.3.3.0100.0.0006 | 6 | 1 | – | 12,3 | 94,1 | 170 | 100/500/1000 |
| 3.644.1.3.3.0100.0.0008 | 8 | 1 | – | 12,7 | 123,9 | 212 | 100/500/1000 |
| 3.644.1.3.3.0100.0.0010 | 10 | 1 | – | 13,1 | 153,6 | 251 | 100/500/1000 |
| 3.644.1.3.3.0100.0.0012 | 12 | 1 | – | 14 | 183,4 | 290 | 100/500/1000 |
| 3.644.1.3.3.0100.0.0014 | 14 | 1 | – | 15,2 | 213,1 | 339 | 100/500/1000 |
| 3.644.1.3.3.0100.0.0016 | 16 | 1 | – | 16,1 | 242,9 | 381 | 100/500/1000 |
| 3.644.1.3.3.0100.0.0020 | 20 | 1 | – | 18 | 302,4 | 465 | 100/500/1000 |
| Part Number | Pair Count | Conductor Diameter (mm) | Cross Section (mm²) | Approx. Cable Diameter (mm) | Copper Weight (kg/km) | Approx. Weight (kg/km) | Packing Lengths (m) |
|---|---|---|---|---|---|---|---|
| 3.644.1.3.3.0150.0.0001 | 1 | – | 1,5 | 6,8 | 32,2 | 64 | 100/500/1000 |
| 3.644.1.3.3.0150.0.0002 | 2 | – | 1,5 | 7,8 | 59,6 | 105 | 100/500/1000 |
| 3.644.1.3.3.0150.0.0003 | 3 | – | 1,5 | 10,2 | 87,4 | 151 | 100/500/1000 |
| 3.644.1.3.3.0150.0.0004 | 4 | – | 1,5 | 12,5 | 114,9 | 201 | 100/500/1000 |
| 3.644.1.3.3.0150.0.0005 | 5 | – | 1,5 | 13,1 | 142,4 | 238 | 100/500/1000 |
| 3.644.1.3.3.0150.0.0006 | 6 | – | 1,5 | 16,2 | 170 | 297 | 100/500/1000 |
| 3.644.1.3.3.0150.0.0008 | 8 | – | 1,5 | 16,9 | 225 | 377 | 100/500/1000 |
| 3.644.1.3.3.0150.0.0010 | 10 | – | 1,5 | 17,4 | 280 | 448 | 100/500/1000 |
| Part Number | Pair Count | Conductor Diameter (mm) | Cross Section (mm²) | Approx. Cable Diameter (mm) | Copper Weight (kg/km) | Approx. Weight (kg/km) | Packing Lengths (m) |
|---|---|---|---|---|---|---|---|
| 3.644.1.3.3.0250.0.0001 | 1 | – | 2,5 | 7,8 | 49,7 | 90 | 100/500/1000 |
| 3.644.1.3.3.0250.0.0002 | 2 | – | 2,5 | 9 | 94,5 | 151 | 100/500/1000 |
| 3.644.1.3.3.0250.0.0003 | 3 | – | 2,5 | 11,9 | 140 | 219 | 100/500/1000 |
| 3.644.1.3.3.0250.0.0004 | 4 | – | 2,5 | 14,5 | 185 | 289 | 100/500/1000 |
| 3.644.1.3.3.0250.0.0005 | 5 | – | 2,5 | 15,1 | 230,1 | 346 | 100/500/1000 |
| 3.644.1.3.3.0250.0.0006 | 6 | – | 2,5 | 18,9 | 275,1 | 429 | 100/500/1000 |
| 3.644.1.3.3.0250.0.0008 | 8 | – | 2,5 | 19,7 | 365,2 | 549 | 100/500/1000 |
| 3.644.1.3.3.0250.0.0010 | 10 | – | 2,5 | 20,3 | 455,3 | 660 | 100/500/1000 |
| Bending Radius | Temperature Range Operating |
|---|---|
| 10xD mm | -30°C ~ +70°C |
J-H(St)H Lg Cable for Halogen-Free Fire Alarm Wiring
J-H(St)H Lg cable is a screened, halogen-free fire alarm cable for fixed indoor signal and communication wiring. ETK Kablo manufactures this cable with solid copper conductors, halogen-free insulation and a red LSZH outer sheath.
Part of our fire alarm cable range, it serves projects that specify low-smoke, halogen-free materials and an overall metallic screen. Applications include compatible fire detection circuits, security systems, intercom wiring and indoor monitoring equipment.
Screening for Alarm and Communication Circuits
An Al/PET foil screen surrounds the cable core, with a tinned copper drain wire for screen termination. Correct installation and earthing help reduce the effects of external electrical interference on the signal circuits.
The two-pair construction uses a star-quad arrangement, while higher pair counts use pairs assembled in layers. Select the conductor arrangement and size to match the equipment specification, cable route and permitted circuit length.
LSZH and Flame-Retardant Performance
The halogen-free insulation and sheath support installations with specified smoke and halogen requirements. The product documentation lists smoke testing to IEC 61034-2, halogen and corrosive-gas testing to IEC 60754-1 and IEC 60754-2, and flame tests to IEC 60332-1-2 and IEC 60332-3-24.
These characteristics do not establish continued circuit operation during fire. Where a project requires FE180 or PH120 performance, consider JE-H(St)H Bd FE180 PH120 fire-resistant cable and confirm its suitability against the project requirements.
J-H(St)H Lg Cable Sizes
The table below lists selected configurations with 0.8 mm diameter conductors. In J-H(St)H Lg 2x2x0.8, the designation identifies two pairs, four insulated conductors and a conductor diameter of 0.8 mm.
| Cable Size | Pair Count | Conductor Count | Conductor Diameter |
|---|---|---|---|
| J-H(St)H Lg 1x2x0.8 | 1 | 2 | 0.8 mm |
| J-H(St)H Lg 2x2x0.8 | 2 | 4 | 0.8 mm |
| J-H(St)H Lg 3x2x0.8 | 3 | 6 | 0.8 mm |
| J-H(St)H Lg 4x2x0.8 | 4 | 8 | 0.8 mm |
| J-H(St)H Lg 5x2x0.8 | 5 | 10 | 0.8 mm |
| J-H(St)H Lg 6x2x0.8 | 6 | 12 | 0.8 mm |
| J-H(St)H Lg 8x2x0.8 | 8 | 16 | 0.8 mm |
| J-H(St)H Lg 10x2x0.8 | 10 | 20 | 0.8 mm |
| J-H(St)H Lg 20x2x0.8 | 20 | 40 | 0.8 mm |
| J-H(St)H Lg 50x2x0.8 | 50 | 100 | 0.8 mm |
| J-H(St)H Lg 100x2x0.8 | 100 | 200 | 0.8 mm |
The Types section also lists additional pair counts, 0.6 mm and 1.0 mm conductor diameters, and 1.5 mm² and 2.5 mm² conductor cross-sections. Refer to that section for part numbers, cable diameters, weights and packing lengths.
Frequently Asked Questions
What is the difference between J-H(St)H Lg and J-Y(St)Y Lg?
J-H(St)H Lg uses halogen-free insulation and an LSZH outer sheath. J-Y(St)Y Lg fire alarm cable uses PVC insulation and a PVC sheath. Choose the material system specified for the installation.
Does 2x2x0.8 mean a conductor cross-section of 0.8 mm²?
No. The final value is the conductor diameter in millimetres. J-H(St)H Lg 2x2x0.8 contains four insulated conductors in a star-quad arrangement, each with a diameter of 0.8 mm.
Is J-H(St)H Lg a PH120 fire-resistant cable?
The published specification lists flame, smoke and halogen tests, but does not state a PH120 circuit-integrity classification. For circuits that must remain operational during fire, select a cable with the required documented fire-resistance rating.
Request a J-H(St)H Lg Cable Quotation
Contact ETK Kablo with the cable size, total quantity, preferred drum lengths and installation requirements. Include any required CPR classification or approval documents so our team can confirm the suitable specification and supply details.