| 1 – Conductor | : | Stranded electrolytic copper conductor (Class 5) (IEC 60228, EN 60228, DIN VDE 0295) |
| 2 – Insulation | : | Cross-linked polymer compound in ceramic form (DIN 47100) |
| 3 – Stranding | : | In layers |
| 4 – Wrapping | : | Polyester tape, glass yarn tape |
| 5 – Screen | : | Tinned copper earthing wire, Al/PET tape |
| 6 – Outer Jacket | : | UV resistant halogen-free outer jacket. RAL 2008 (Orange) |
| Conductor Diameter | Conductor Resistance Ω/km (20 °C) | Insulation Resistance (@500V DC) MΩ/km | Mutual Capacitance nF/km | Operating Voltage V DC | Test Voltage (@ 1 minute) V DC |
|---|---|---|---|---|---|
| 0.50 mm² | 39.0 | 100 | 100 | 300 | 2000 |
| 0.75 mm² | 26.0 | 100 | 100 | 300 | 2000 |
| 1.00 mm² | 19.5 | 100 | 100 | 300 | 2000 |
| 1.50 mm² | 13.3 | 100 | 100 | 300 | 2000 |
| 2.50 mm² | 8.0 | 100 | 100 | 300 | 2000 |
| Smoke Density Test | Corrosive Gas Test | Halogen-free Test | Flame Propagation Test | Flame Retardancy Test |
|---|---|---|---|---|
| IEC 61034-2, VDE 0482-1034-2, BS EN 61034-2 | IEC 60754-2, VDE 0482-267-2-3, BS EN 50267-2-3 | IEC 60754-1, VDE 0482-267-2-1, BS EN 50267-2-1 | IEC 60332-3-24, VDE 0482-332-3-24, EN 60332-2-24 | IEC 60332-1-2, VDE 0482-332-1-2, BS EN 60332-1-2 |
| Circuit Integrity Test (FE180) | Circuit Integrity with Shock Test (PH120) |
|---|---|
| IEC 60331-21 | EN 50200, VDE 0482-200, BS EN 50200 |
| Part Number | ConductorCount | Conductor Diameter (mm²) | Approx. Cable Diameter(mm) | Copper Weight(kg/km) | Approx. Weight (kg/km) | Packing Lengths (m) |
|---|---|---|---|---|---|---|
| 3.545.2.4.3.0050.0.0002 | 2 | 0,5 | 5,8 | 11,1 | 34 | 100/500/1000 |
| 3.545.2.4.3.0050.0.0003 | 3 | 0,5 | 6,1 | 15,5 | 47 | 100/500/1000 |
| 3.545.2.4.3.0050.0.0004 | 4 | 0,5 | 6,5 | 19,9 | 56 | 100/500/1000 |
| 3.545.3.4.3.0050.0.0005 | 5 | 0,5 | 7,1 | 24,3 | 67 | 100/500/1000 |
| 3.545.3.4.3.0050.0.0006 | 6 | 0,5 | 7,7 | 28,7 | 81 | 100/500/1000 |
| 3.545.3.4.3.0050.0.0007 | 7 | 0,5 | 7,7 | 33,2 | 84 | 100/500/1000 |
| 3.545.3.4.3.0050.0.0008 | 8 | 0,5 | 8,4 | 37,4 | 101 | 100/500/1000 |
| 3.545.3.4.3.0050.0.0009 | 9 | 0,5 | 9,6 | 41,8 | 115 | 100/500/1000 |
| 3.545.3.4.3.0050.0.0010 | 10 | 0,5 | 9,6 | 46,2 | 118 | 100/500/1000 |
| 3.545.3.4.3.0050.0.0012 | 12 | 0,5 | 10 | 55 | 136 | 100/500/1000 |
| 3.545.3.4.3.0050.0.0014 | 14 | 0,5 | 10,5 | 63,8 | 155 | 100/500/1000 |
| 3.545.3.4.3.0050.0.0016 | 16 | 0,5 | 11,1 | 72,6 | 171 | 100/500/1000 |
| 3.545.3.4.3.0050.0.0018 | 18 | 0,5 | 11,6 | 81,4 | 192 | 100/500/1000 |
| 3.545.3.4.3.0050.0.0019 | 19 | 0,5 | 11,6 | 85,8 | 195 | 100/500/1000 |
| 3.545.3.4.3.0050.0.0020 | 20 | 0,5 | 12,3 | 90,2 | 215 | 100/500/1000 |
| 3.545.3.4.3.0050.0.0021 | 21 | 0,5 | 12,3 | 94,6 | 227 | 100/500/1000 |
| 3.545.3.4.3.0050.0.0024 | 24 | 0,5 | 13,4 | 107,9 | 244 | 100/500/1000 |
| 3.545.3.4.3.0050.0.0025 | 25 | 0,5 | 13,6 | 112,3 | 265 | 100/500/1000 |
| 3.545.3.4.3.0050.0.0027 | 27 | 0,5 | 13,9 | 121,1 | 273 | 100/500/1000 |
| Part Number | ConductorCount | Conductor Diameter (mm²) | Approx. Cable Diameter(mm) | Copper Weight(kg/km) | Approx. Weight (kg/km) | Packing Lengths (m) |
|---|---|---|---|---|---|---|
| 3.545.2.4.3.0075.0.0002 | 2 | 0,75 | 6,5 | 17,7 | 50 | 100/500/1000 |
| 3.545.2.4.3.0075.0.0003 | 3 | 0,75 | 6,8 | 24,3 | 61 | 100/500/1000 |
| 3.545.2.4.3.0075.0.0004 | 4 | 0,75 | 7,4 | 30,9 | 75 | 100/500/1000 |
| 3.545.3.4.3.0075.0.0005 | 5 | 0,75 | 8 | 37,5 | 91 | 100/500/1000 |
| 3.545.3.4.3.0075.0.0006 | 6 | 0,75 | 8,6 | 44,1 | 101 | 100/500/1000 |
| 3.545.3.4.3.0075.0.0007 | 7 | 0,75 | 8,6 | 50,7 | 111 | 100/500/1000 |
| 3.545.3.4.3.0075.0.0008 | 8 | 0,75 | 9,4 | 57,3 | 133 | 100/500/1000 |
| 3.545.3.4.3.0075.0.0009 | 9 | 0,75 | 10,8 | 63,9 | 151 | 100/500/1000 |
| 3.545.3.4.3.0075.0.0010 | 10 | 0,75 | 10,8 | 70,5 | 155 | 100/500/1000 |
| 3.545.3.4.3.0075.0.0012 | 12 | 0,75 | 11,2 | 83,7 | 179 | 100/500/1000 |
| 3.545.3.4.3.0075.0.0014 | 14 | 0,75 | 11,8 | 96,9 | 204 | 100/500/1000 |
| 3.545.3.4.3.0075.0.0016 | 16 | 0,75 | 12,3 | 110,1 | 226 | 100/500/1000 |
| 3.545.3.4.3.0075.0.0018 | 18 | 0,75 | 13 | 123,3 | 257 | 100/500/1000 |
| 3.545.3.4.3.0075.0.0019 | 19 | 0,75 | 13 | 129,9 | 262 | 100/500/1000 |
| 3.545.3.4.3.0075.0.0020 | 20 | 0,75 | 13,7 | 136,5 | 283 | 100/500/1000 |
| 3.545.3.4.3.0075.0.0021 | 21 | 0,75 | 13,7 | 143,1 | 285 | 100/500/1000 |
| 3.545.3.4.3.0075.0.0024 | 24 | 0,75 | 15,2 | 162,9 | 329 | 100/500/1000 |
| 3.545.3.4.3.0075.0.0025 | 25 | 0,75 | 15,2 | 169,5 | 348 | 100/500/1000 |
| 3.545.3.4.3.0075.0.0027 | 27 | 0,75 | 15,5 | 182,7 | 360 | 100/500/1000 |
| Part Number | ConductorCount | Conductor Diameter (mm²) | Approx. Cable Diameter(mm) | Copper Weight(kg/km) | Approx. Weight (kg/km) | Packing Lengths (m) |
|---|---|---|---|---|---|---|
| 3.545.2.4.3.0100.0.0002 | 2 | 1 | 6,9 | 21 | 57 | 100/500/1000 |
| 3.545.2.4.3.0100.0.0003 | 3 | 1 | 7,2 | 29,2 | 70 | 100/500/1000 |
| 3.545.3.4.3.0100.0.0004 | 4 | 1 | 7,8 | 37,5 | 86 | 100/500/1000 |
| 3.545.3.4.3.0100.0.0005 | 5 | 1 | 8,6 | 45,8 | 106 | 100/500/1000 |
| 3.545.3.4.3.0100.0.0006 | 6 | 1 | 9,2 | 54 | 124 | 100/500/1000 |
| 3.545.3.4.3.0100.0.0007 | 7 | 1 | 9,2 | 62,3 | 130 | 100/500/1000 |
| 3.545.3.4.3.0100.0.0008 | 8 | 1 | 10,1 | 70,5 | 155 | 100/500/1000 |
| 3.545.3.4.3.0100.0.0009 | 9 | 1 | 11,6 | 78,7 | 176 | 100/500/1000 |
| 3.545.3.4.3.0100.0.0010 | 10 | 1 | 11,6 | 87 | 182 | 100/500/1000 |
| 3.545.3.4.3.0100.0.0012 | 12 | 1 | 12 | 103,5 | 210 | 100/500/1000 |
| 3.545.3.4.3.0100.0.0014 | 14 | 1 | 12,6 | 120 | 240 | 100/500/1000 |
| 3.545.3.4.3.0100.0.0016 | 16 | 1 | 13,3 | 136,5 | 268 | 100/500/1000 |
| 3.545.3.4.3.0100.0.0018 | 18 | 1 | 14 | 153 | 304 | 100/500/1000 |
| 3.545.3.4.3.0100.0.0019 | 19 | 1 | 14 | 161,3 | 310 | 100/500/1000 |
| 3.545.3.4.3.0100.0.0020 | 20 | 1 | 14,7 | 169,5 | 335 | 100/500/1000 |
| 3.545.3.4.3.0100.0.0021 | 21 | 1 | 14,7 | 177,8 | 338 | 100/500/1000 |
| 3.545.3.4.3.0100.0.0024 | 24 | 1 | 16,3 | 202,5 | 387 | 100/500/1000 |
| 3.545.3.4.3.0100.0.0025 | 25 | 1 | 16,3 | 210,8 | 409 | 100/500/1000 |
| 3.545.3.4.3.0100.0.0027 | 27 | 1 | 16,6 | 227,3 | 423 | 100/500/1000 |
| Part Number | ConductorCount | Conductor Diameter (mm²) | Approx. Cable Diameter(mm) | Copper Weight(kg/km) | Approx. Weight (kg/km) | Packing Lengths (m) |
|---|---|---|---|---|---|---|
| 3.545.2.4.3.0150.0.0002 | 2 | 1,5 | 7,5 | 30,2 | 71 | 100/500/1000 |
| 3.545.2.4.3.0150.0.0003 | 3 | 1,5 | 7,9 | 43,1 | 89 | 100/500/1000 |
| 3.545.2.4.3.0150.0.0004 | 4 | 1,5 | 8,6 | 56 | 111 | 100/500/1000 |
| 3.545.3.4.3.0150.0.0005 | 5 | 1,5 | 9,3 | 68,8 | 136 | 100/500/1000 |
| 3.545.3.4.3.0150.0.0006 | 6 | 1,5 | 10,1 | 81,7 | 160 | 100/500/1000 |
| 3.545.3.4.3.0150.0.0007 | 7 | 1,5 | 10,1 | 94,5 | 170 | 100/500/1000 |
| 3.545.3.4.3.0150.0.0008 | 8 | 1,5 | 11 | 107,3 | 203 | 100/500/1000 |
| 3.545.3.4.3.0150.0.0009 | 9 | 1,5 | 12,7 | 120,2 | 230 | 100/500/1000 |
| 3.545.3.4.3.0150.0.0010 | 10 | 1,5 | 12,7 | 133,1 | 239 | 100/500/1000 |
| 3.545.3.4.3.0150.0.0012 | 12 | 1,5 | 13,2 | 158,8 | 278 | 100/500/1000 |
| 3.545.3.4.3.0150.0.0014 | 14 | 1,5 | 13,9 | 184,5 | 318 | 100/500/1000 |
| 3.545.3.4.3.0150.0.0016 | 16 | 1,5 | 14,5 | 210,2 | 355 | 100/500/1000 |
| 3.545.3.4.3.0150.0.0018 | 18 | 1,5 | 15,4 | 235,9 | 403 | 100/500/1000 |
| 3.545.3.4.3.0150.0.0019 | 19 | 1,5 | 15,4 | 248,8 | 413 | 100/500/1000 |
| 3.545.3.4.3.0150.0.0020 | 20 | 1,5 | 16,2 | 261,7 | 446 | 100/500/1000 |
| 3.545.3.4.3.0150.0.0021 | 21 | 1,5 | 16,2 | 274,5 | 451 | 100/500/1000 |
| 3.545.3.4.3.0150.0.0024 | 24 | 1,5 | 18 | 313,1 | 520 | 100/500/1000 |
| 3.545.3.4.3.0150.0.0025 | 25 | 1,5 | 18 | 326 | 549 | 100/500/1000 |
| 3.545.3.4.3.0150.0.0027 | 27 | 1,5 | 18,3 | 351,7 | 571 | 100/500/1000 |
| Part Number | ConductorCount | Conductor Diameter (mm²) | Approx. Cable Diameter(mm) | Copper Weight(kg/km) | Approx. Weight (kg/km) | Packing Lengths (m) |
|---|---|---|---|---|---|---|
| 3.545.2.4.3.0250.0.0002 | 2 | 2,5 | 8,7 | 47,4 | 97 | 100/500/1000 |
| 3.545.2.4.3.0250.0.0003 | 3 | 2,5 | 9,1 | 68,8 | 126 | 100/500/1000 |
| 3.545.2.4.3.0250.0.0004 | 4 | 2,5 | 10 | 90,2 | 159 | 100/500/1000 |
| 3.545.3.4.3.0250.0.0005 | 5 | 2,5 | 11 | 111,7 | 198 | 100/500/1000 |
| 3.545.3.4.3.0250.0.0006 | 6 | 2,5 | 11,9 | 133,1 | 235 | 100/500/1000 |
| 3.545.3.4.3.0250.0.0007 | 7 | 2,5 | 11,9 | 154,5 | 252 | 100/500/1000 |
| 3.545.3.4.3.0250.0.0008 | 8 | 2,5 | 13 | 175,9 | 300 | 100/500/1000 |
| 3.545.3.4.3.0250.0.0009 | 9 | 2,5 | 15,1 | 197,4 | 340 | 100/500/1000 |
| 3.545.3.4.3.0250.0.0010 | 10 | 2,5 | 15,1 | 218,8 | 356 | 100/500/1000 |
| 3.545.3.4.3.0250.0.0012 | 12 | 2,5 | 15,6 | 261,7 | 416 | 100/500/1000 |
| 3.545.3.4.3.0250.0.0014 | 14 | 2,5 | 16,5 | 304,5 | 478 | 100/500/1000 |
| 3.545.3.4.3.0250.0.0016 | 16 | 2,5 | 17,4 | 347,4 | 536 | 100/500/1000 |
| 3.545.3.4.3.0250.0.0018 | 18 | 2,5 | 18,4 | 390,2 | 610 | 100/500/1000 |
| 3.545.3.4.3.0250.0.0019 | 19 | 2,5 | 18,4 | 411,7 | 626 | 100/500/1000 |
| 3.545.3.4.3.0250.0.0020 | 20 | 2,5 | 19,4 | 433,1 | 677 | 100/500/1000 |
| 3.545.3.4.3.0250.0.0021 | 21 | 2,5 | 19,4 | 454,5 | 686 | 100/500/1000 |
| 3.545.3.4.3.0250.0.0024 | 24 | 2,5 | 21,6 | 518,8 | 784 | 100/500/1000 |
| 3.545.3.4.3.0250.0.0025 | 25 | 2,5 | 21,6 | 540,3 | 838 | 100/500/1000 |
| 3.545.3.4.3.0250.0.0027 | 27 | 2,5 | 22 | 583,1 | 873 | 100/500/1000 |
| Bending Radius | Temperature Range Operating |
|---|---|
| 10xD mm | -40°C ~ +70°C |
LIH(St)H FE180 PH120 Foil Screened Fire Resistant Cable
LIH(St)H FE180 PH120 is a halogen-free signal and control cable with an overall aluminium/polyester foil screen. ETK Kablo manufactures this cable with flexible Class 5 copper conductors, ceramic-forming insulation and an orange LSZH outer jacket. It belongs to our fire resistant cable range for circuits with specified fire integrity requirements.
Signal Transmission and Control Applications
Typical applications include instrumentation, industrial electronics, indoor communication, sound systems, security and fire alarm circuits. Select the conductor count and cross-section according to the equipment requirements, circuit length and project specification.
The overall Al/PET screen and tinned copper drain wire help reduce electromagnetic interference when correctly terminated. The insulated cores are stranded in layers within a common screen. This is a multicore construction, rather than an individually screened pair design.
FE180 and PH120 Performance
FE180 describes cable integrity for 180 minutes under the specified fire test conditions. PH120 describes circuit integrity for 120 minutes under fire and mechanical shock testing according to EN 50200. These classifications describe laboratory test performance, rather than guaranteed operating time in every fire.
Low smoke and halogen-free properties address separate requirements. The product documentation lists IEC 61034-2 for smoke density, IEC 60754-1 and IEC 60754-2 for halogen and corrosive gas characteristics, and IEC 60332-1-2 and IEC 60332-3-24 for flame propagation performance.
Selected LIH(St)H FE180 PH120 Cable Sizes
The table below lists selected configurations from the product range. For the full list, dimensions, weights and packing lengths, see the Types section on this page.
| Cable Size | Conductor Count | Conductor Cross-section (mm²) |
|---|---|---|
| LIH(St)H FE180 PH120 2×0.50 mm² | 2 | 0.50 |
| LIH(St)H FE180 PH120 4×0.50 mm² | 4 | 0.50 |
| LIH(St)H FE180 PH120 2×0.75 mm² | 2 | 0.75 |
| LIH(St)H FE180 PH120 4×0.75 mm² | 4 | 0.75 |
| LIH(St)H FE180 PH120 7×0.75 mm² | 7 | 0.75 |
| LIH(St)H FE180 PH120 12×0.75 mm² | 12 | 0.75 |
| LIH(St)H FE180 PH120 2×1.00 mm² | 2 | 1.00 |
| LIH(St)H FE180 PH120 4×1.00 mm² | 4 | 1.00 |
| LIH(St)H FE180 PH120 4×1.50 mm² | 4 | 1.50 |
| LIH(St)H FE180 PH120 4×2.50 mm² | 4 | 2.50 |
Frequently Asked Questions
How does LIH(St)H differ from LIHCH FE180 PH120?
LIH(St)H FE180 PH120 uses an overall aluminium/polyester foil screen with a drain wire. The separate LIHCH FE180 PH120 cable uses a tinned copper braid screen. Choose the screening construction required by the application.
What does 2×0.75 mm² mean?
It means two insulated conductors, each with a cross-section of 0.75 mm². The number refers to conductor area, not diameter. A paired designation such as 2x2x0.75 describes a different arrangement.
Does FE180 PH120 also mean E90?
No. FE180 and PH120 describe cable-level fire performance. E90 concerns the functional integrity of a tested cable installation system, including its supports and fixings. This product’s published specification does not list an E90 classification.
Request a LIH(St)H FE180 PH120 Quotation
Contact ETK Kablo with your required conductor count, cross-section, cable length and installation conditions. Include the project fire test requirements and any supporting documentation needed for product selection.