| 1 – Conductor | : | Stranded electrolytic copper conductor (Class 5) (IEC 60228, EN 60228, DIN VDE 0295) |
| 2 – Insulation | : | Cross-linked polymer compound in ceramic form (DIN 47100) |
| 3 – Stranding | : | In layers |
| 4 – Wrapping | : | Polyester tape, glass yarn tape |
| 5 – Screen | : | Tinned copper braiding |
| 6 – Outer Jacket | : | UV resistant halogen-free outer jacket. RAL 2008 (Orange) |
| Conductor Diameter | Conductor Resistance Ω/km (20 °C) | Insulation Resistance (@500V DC) MΩ/km | Mutual Capacitance nF/km | Operating Voltage V DC | Test Voltage (@ 1 minute) V DC |
|---|---|---|---|---|---|
| 0.50 mm² | 39.0 | 100 | 100 | 300 | 2000 |
| 0.75 mm² | 26.0 | 100 | 100 | 300 | 2000 |
| 1.00 mm² | 19.5 | 100 | 100 | 300 | 2000 |
| 1.50 mm² | 13.3 | 100 | 100 | 300 | 2000 |
| 2.50 mm² | 8.0 | 100 | 100 | 300 | 2000 |
| Smoke Density Test | Corrosive Gas Test | Halogen-free Test | Flame Propagation Test | Flame Retardancy Test |
|---|---|---|---|---|
| IEC 61034-2, VDE 0482-1034-2, BS EN 61034-2 | IEC 60754-2, VDE 0482-267-2-3, BS EN 50267-2-3 | IEC 60754-1, VDE 0482-267-2-1, BS EN 50267-2-1 | IEC 60332-3-24, VDE 0482-332-3-24, EN 60332-2-24 | IEC 60332-1-2, VDE 0482-332-1-2, BS EN 60332-1-2 |
| Circuit Integrity Test (FE180) | Circuit Integrity with Shock Test (PH120) |
|---|---|
| IEC 60331-21 | EN 50200, VDE 0482-200, BS EN 50200 |
| Part Number | ConductorCount | Conductor Diameter (mm²) | Approx. Cable Diameter(mm) | Copper Weight(kg/km) | Approx. Weight (kg/km) | Packing Lengths (m) |
|---|---|---|---|---|---|---|
| 3.517.2.4.3.0050.0.0002 | 2 | 0,5 | 5,6 | 16,9 | 43 | 100/500/1000 |
| 3.517.2.4.3.0050.0.0003 | 3 | 0,5 | 5,9 | 21,3 | 51 | 100/500/1000 |
| 3.517.2.4.3.0050.0.0004 | 4 | 0,5 | 6,3 | 26,1 | 60 | 100/500/1000 |
| 3.517.3.4.3.0050.0.0005 | 5 | 0,5 | 7 | 31,6 | 73 | 100/500/1000 |
| 3.517.3.4.3.0050.0.0006 | 6 | 0,5 | 7,5 | 37,7 | 86 | 100/500/1000 |
| 3.517.3.4.3.0050.0.0007 | 7 | 0,5 | 7,5 | 42,1 | 89 | 100/500/1000 |
| 3.517.3.4.3.0050.0.0008 | 8 | 0,5 | 8,2 | 47 | 107 | 100/500/1000 |
| 3.517.3.4.3.0050.0.0009 | 9 | 0,5 | 9,4 | 52,6 | 122 | 100/500/1000 |
| 3.517.3.4.3.0050.0.0010 | 10 | 0,5 | 9,4 | 57,8 | 125 | 100/500/1000 |
| 3.517.3.4.3.0050.0.0012 | 12 | 0,5 | 9,9 | 69,8 | 146 | 100/500/1000 |
| 3.517.3.4.3.0050.0.0014 | 14 | 0,5 | 10,4 | 80,9 | 167 | 100/500/1000 |
| 3.517.3.4.3.0050.0.0016 | 16 | 0,5 | 10,9 | 90,2 | 184 | 100/500/1000 |
| 3.517.3.4.3.0050.0.0018 | 18 | 0,5 | 11,5 | 96,2 | 205 | 100/500/1000 |
| 3.517.3.4.3.0050.0.0019 | 19 | 0,5 | 11,5 | 100,6 | 208 | 100/500/1000 |
| 3.517.3.4.3.0050.0.0020 | 20 | 0,5 | 12,1 | 106,7 | 226 | 100/500/1000 |
| 3.517.3.4.3.0050.0.0021 | 21 | 0,5 | 12,1 | 111,1 | 227 | 100/500/1000 |
| 3.517.3.4.3.0050.0.0024 | 24 | 0,5 | 13,4 | 126 | 263 | 100/500/1000 |
| 3.517.3.4.3.0050.0.0025 | 25 | 0,5 | 13,4 | 130,4 | 277 | 100/500/1000 |
| 3.517.3.4.3.0050.0.0027 | 27 | 0,5 | 13,7 | 140,6 | 286 | 100/500/1000 |
| Part Number | ConductorCount | Conductor Diameter (mm²) | Approx. Cable Diameter(mm) | Copper Weight(kg/km) | Approx. Weight (kg/km) | Packing Lengths (m) |
|---|---|---|---|---|---|---|
| 3.517.2.4.3.0075.0.0002 | 2 | 0,75 | 6,1 | 21,6 | 51 | 100/500/1000 |
| 3.517.2.4.3.0075.0.0003 | 3 | 0,75 | 6,4 | 28,2 | 62 | 100/500/1000 |
| 3.517.2.4.3.0075.0.0004 | 4 | 0,75 | 7 | 36 | 76 | 100/500/1000 |
| 3.517.3.4.3.0075.0.0005 | 5 | 0,75 | 7,7 | 43,6 | 94 | 100/500/1000 |
| 3.517.3.4.3.0075.0.0006 | 6 | 0,75 | 8,3 | 52 | 110 | 100/500/1000 |
| 3.517.3.4.3.0075.0.0007 | 7 | 0,75 | 8,3 | 58,6 | 115 | 100/500/1000 |
| 3.517.3.4.3.0075.0.0008 | 8 | 0,75 | 9,1 | 66,2 | 138 | 100/500/1000 |
| 3.517.3.4.3.0075.0.0009 | 9 | 0,75 | 10,5 | 76,6 | 158 | 100/500/1000 |
| 3.517.3.4.3.0075.0.0010 | 10 | 0,75 | 10,5 | 84,2 | 164 | 100/500/1000 |
| 3.517.3.4.3.0075.0.0012 | 12 | 0,75 | 10,9 | 98,9 | 189 | 100/500/1000 |
| 3.517.3.4.3.0075.0.0014 | 14 | 0,75 | 11,4 | 109,4 | 211 | 100/500/1000 |
| 3.517.3.4.3.0075.0.0016 | 16 | 0,75 | 12 | 124,2 | 234 | 100/500/1000 |
| 3.517.3.4.3.0075.0.0018 | 18 | 0,75 | 12,7 | 138,7 | 266 | 100/500/1000 |
| 3.517.3.4.3.0075.0.0019 | 19 | 0,75 | 12,7 | 145,3 | 271 | 100/500/1000 |
| 3.517.3.4.3.0075.0.0020 | 20 | 0,75 | 13,4 | 157,1 | 296 | 100/500/1000 |
| 3.517.3.4.3.0075.0.0021 | 21 | 0,75 | 13,4 | 163,7 | 299 | 100/500/1000 |
| 3.517.3.4.3.0075.0.0024 | 24 | 0,75 | 14,9 | 185,5 | 344 | 100/500/1000 |
| 3.517.3.4.3.0075.0.0025 | 25 | 0,75 | 14,9 | 192,1 | 363 | 100/500/1000 |
| 3.517.3.4.3.0075.0.0027 | 27 | 0,75 | 15,2 | 207,2 | 376 | 100/500/1000 |
| Part Number | ConductorCount | Conductor Diameter (mm²) | Approx. Cable Diameter(mm) | Copper Weight(kg/km) | Approx. Weight (kg/km) | Packing Lengths (m) |
|---|---|---|---|---|---|---|
| 3.517.2.4.3.0100.0.0002 | 2 | 1 | 6,5 | 26 | 58 | 100/500/1000 |
| 3.517.2.4.3.0100.0.0003 | 3 | 1 | 6,9 | 34,3 | 72 | 100/500/1000 |
| 3.517.3.4.3.0100.0.0004 | 4 | 1 | 7,5 | 43,5 | 89 | 100/500/1000 |
| 3.517.3.4.3.0100.0.0005 | 5 | 1 | 8,2 | 52,2 | 108 | 100/500/1000 |
| 3.517.3.4.3.0100.0.0006 | 6 | 1 | 8,9 | 66,2 | 131 | 100/500/1000 |
| 3.517.3.4.3.0100.0.0007 | 7 | 1 | 8,9 | 74,4 | 138 | 100/500/1000 |
| 3.517.3.4.3.0100.0.0008 | 8 | 1 | 9,8 | 83,8 | 164 | 100/500/1000 |
| 3.517.3.4.3.0100.0.0009 | 9 | 1 | 11,2 | 91,2 | 183 | 100/500/1000 |
| 3.517.3.4.3.0100.0.0010 | 10 | 1 | 11,2 | 99,5 | 189 | 100/500/1000 |
| 3.517.3.4.3.0100.0.0012 | 12 | 1 | 11,7 | 116,7 | 218 | 100/500/1000 |
| 3.517.3.4.3.0100.0.0014 | 14 | 1 | 12,3 | 134 | 248 | 100/500/1000 |
| 3.517.3.4.3.0100.0.0016 | 16 | 1 | 12,9 | 152,1 | 277 | 100/500/1000 |
| 3.517.3.4.3.0100.0.0018 | 18 | 1 | 13,7 | 173,8 | 318 | 100/500/1000 |
| 3.517.3.4.3.0100.0.0019 | 19 | 1 | 13,7 | 182 | 324 | 100/500/1000 |
| 3.517.3.4.3.0100.0.0020 | 20 | 1 | 14,4 | 192 | 350 | 100/500/1000 |
| 3.517.3.4.3.0100.0.0021 | 21 | 1 | 14,4 | 200,2 | 353 | 100/500/1000 |
| 3.517.3.4.3.0100.0.0024 | 24 | 1 | 16 | 227,9 | 404 | 100/500/1000 |
| 3.517.3.4.3.0100.0.0025 | 25 | 1 | 16 | 236,1 | 426 | 100/500/1000 |
| 3.517.3.4.3.0100.0.0027 | 27 | 1 | 16,3 | 255,2 | 443 | 100/500/1000 |
| Part Number | ConductorCount | Conductor Diameter (mm²) | Approx. Cable Diameter(mm) | Copper Weight(kg/km) | Approx. Weight (kg/km) | Packing Lengths (m) |
|---|---|---|---|---|---|---|
| 3.517.2.4.3.0150.0.0002 | 2 | 1,5 | 7,1 | 35,7 | 73 | 100/500/1000 |
| 3.517.2.4.3.0150.0.0003 | 3 | 1,5 | 7,5 | 48,7 | 91 | 100/500/1000 |
| 3.517.2.4.3.0150.0.0004 | 4 | 1,5 | 8,2 | 62,8 | 113 | 100/500/1000 |
| 3.517.3.4.3.0150.0.0005 | 5 | 1,5 | 9 | 76,9 | 140 | 100/500/1000 |
| 3.517.3.4.3.0150.0.0006 | 6 | 1,5 | 9,8 | 94,9 | 169 | 100/500/1000 |
| 3.517.3.4.3.0150.0.0007 | 7 | 1,5 | 9,8 | 107,8 | 178 | 100/500/1000 |
| 3.517.3.4.3.0150.0.0008 | 8 | 1,5 | 10,7 | 119,7 | 210 | 100/500/1000 |
| 3.517.3.4.3.0150.0.0009 | 9 | 1,5 | 12,3 | 132,9 | 236 | 100/500/1000 |
| 3.517.3.4.3.0150.0.0010 | 10 | 1,5 | 12,3 | 147,2 | 247 | 100/500/1000 |
| 3.517.3.4.3.0150.0.0012 | 12 | 1,5 | 12,8 | 174,2 | 287 | 100/500/1000 |
| 3.517.3.4.3.0150.0.0014 | 14 | 1,5 | 13,6 | 205,1 | 331 | 100/500/1000 |
| 3.517.3.4.3.0150.0.0016 | 16 | 1,5 | 14,3 | 232,4 | 370 | 100/500/1000 |
| 3.517.3.4.3.0150.0.0018 | 18 | 1,5 | 15,1 | 260,2 | 420 | 100/500/1000 |
| 3.517.3.4.3.0150.0.0019 | 19 | 1,5 | 15,1 | 273,1 | 429 | 100/500/1000 |
| 3.517.3.4.3.0150.0.0020 | 20 | 1,5 | 15,9 | 286,6 | 463 | 100/500/1000 |
| 3.517.3.4.3.0150.0.0021 | 21 | 1,5 | 15,9 | 299,5 | 468 | 100/500/1000 |
| 3.517.3.4.3.0150.0.0024 | 24 | 1,5 | 17,7 | 342 | 540 | 100/500/1000 |
| 3.517.3.4.3.0150.0.0025 | 25 | 1,5 | 17,7 | 354,8 | 570 | 100/500/1000 |
| 3.517.3.4.3.0150.0.0027 | 27 | 1,5 | 18 | 381 | 592 | 100/500/1000 |
| Part Number | ConductorCount | Conductor Diameter (mm²) | Approx. Cable Diameter(mm) | Copper Weight(kg/km) | Approx. Weight (kg/km) | Packing Lengths (m) |
|---|---|---|---|---|---|---|
| 3.517.2.4.3.0250.0.0002 | 2 | 2,5 | 8,4 | 58,8 | 105 | 100/500/1000 |
| 3.517.2.4.3.0250.0.0003 | 3 | 2,5 | 8,9 | 80,3 | 134 | 100/500/1000 |
| 3.517.2.4.3.0250.0.0004 | 4 | 2,5 | 9,8 | 103,6 | 170 | 100/500/1000 |
| 3.517.3.4.3.0250.0.0005 | 5 | 2,5 | 10,8 | 124 | 211 | 100/500/1000 |
| 3.517.3.4.3.0250.0.0006 | 6 | 2,5 | 11,7 | 147,9 | 251 | 100/500/1000 |
| 3.517.3.4.3.0250.0.0007 | 7 | 2,5 | 11,7 | 169,3 | 266 | 100/500/1000 |
| 3.517.3.4.3.0250.0.0008 | 8 | 2,5 | 12,9 | 192,5 | 317 | 100/500/1000 |
| 3.517.3.4.3.0250.0.0009 | 9 | 2,5 | 15 | 220,1 | 363 | 100/500/1000 |
| 3.517.3.4.3.0250.0.0010 | 10 | 2,5 | 15 | 243,3 | 381 | 100/500/1000 |
| 3.517.3.4.3.0250.0.0012 | 12 | 2,5 | 15,6 | 286,6 | 441 | 100/500/1000 |
| 3.517.3.4.3.0250.0.0014 | 14 | 2,5 | 16,4 | 332,4 | 506 | 100/500/1000 |
| 3.517.3.4.3.0250.0.0016 | 16 | 2,5 | 17,3 | 378,9 | 568 | 100/500/1000 |
| 3.517.3.4.3.0250.0.0018 | 18 | 2,5 | 18,3 | 423,1 | 644 | 100/500/1000 |
| 3.517.3.4.3.0250.0.0019 | 19 | 2,5 | 18,3 | 444,5 | 659 | 100/500/1000 |
| 3.517.3.4.3.0250.0.0020 | 20 | 2,5 | 19,3 | 467,4 | 712 | 100/500/1000 |
| 3.517.3.4.3.0250.0.0021 | 21 | 2,5 | 19,3 | 488,9 | 721 | 100/500/1000 |
| 3.517.3.4.3.0250.0.0024 | 24 | 2,5 | 21,4 | 559,9 | 827 | 100/500/1000 |
| 3.517.3.4.3.0250.0.0025 | 25 | 2,5 | 21,4 | 581,3 | 874 | 100/500/1000 |
| 3.517.3.4.3.0250.0.0027 | 27 | 2,5 | 21,8 | 628,7 | 913 | 100/500/1000 |
| Part Number | ConductorCount | Conductor Diameter (mm²) | Approx. Cable Diameter(mm) | Copper Weight(kg/km) | Approx. Weight (kg/km) | Packing Lengths (m) |
|---|---|---|---|---|---|---|
| 3.517.3.4.3.0400.0.0002 | 2 | 4 | 9,4 | 83,5 | 138 | 100/500/1000 |
| 3.517.3.4.3.0400.0.0003 | 3 | 4 | 10 | 119 | 181 | 100/500/1000 |
| 3.517.3.4.3.0400.0.0004 | 4 | 4 | 11 | 154,5 | 230 | 100/500/1000 |
| 3.517.3.4.3.0400.0.0005 | 5 | 4 | 12,1 | 191,1 | 287 | 100/500/1000 |
| 3.517.3.4.3.0400.0.0006 | 6 | 4 | 13,2 | 227,3 | 346 | 100/500/1000 |
| 3.517.3.4.3.0400.0.0007 | 7 | 4 | 13,2 | 261,6 | 371 | 100/500/1000 |
| Part Number | ConductorCount | Conductor Diameter (mm²) | Approx. Cable Diameter(mm) | Copper Weight(kg/km) | Approx. Weight (kg/km) | Packing Lengths (m) |
|---|---|---|---|---|---|---|
| 3.517.3.4.3.0600.0.0002 | 2 | 6 | 11,1 | 120,4 | 191 | 100/500/1000 |
| 3.517.3.4.3.0600.0.0003 | 3 | 6 | 11,9 | 173,8 | 260 | 100/500/1000 |
| 3.517.3.4.3.0600.0.0004 | 4 | 6 | 13,1 | 227,2 | 331 | 100/500/1000 |
| 3.517.3.4.3.0600.0.0005 | 5 | 6 | 14,5 | 285,6 | 419 | 100/500/1000 |
| 3.517.3.4.3.0600.0.0006 | 6 | 6 | 15,8 | 340,6 | 501 | 100/500/1000 |
| 3.517.3.4.3.0600.0.0007 | 7 | 6 | 15,8 | 392 | 539 | 100/500/1000 |
| Bending Radius | Temperature Range Operating |
|---|---|
| 10xD mm | -40°C ~ +70°C |
LIHCH FE180 PH120 Fire-Resistant, Halogen-Free Shielded Signal & Control Cable
ETK Kablo’s LIHCH FE180 PH120 is a fire-resistant cable designed for fire-safety critical systems that must remain operational during a blaze. With a copper braid shield (C) for EMI suppression and a Low Smoke Zero Halogen (LSOH) sheath, this fire-safe cable maintains signal integrity while minimizing smoke and toxic emissions.
Certified Fire Performance for Critical Infrastructure
Tested for FE180 (functional integrity of conductors for 180 minutes) and PH120 (circuit integrity for 120 minutes under flame and mechanical stress), the cable supports uninterrupted operation of fire alarm systems, emergency lighting, HVAC control, BMS networks, and energy plant automation. It is the dependable choice when specifying fire resistant cables for high-occupancy or mission-critical buildings.
Halogen-Free Construction & EMI Protection
The LSOH sheath significantly reduces smoke density and corrosive gases, supporting safe evacuation and equipment protection. A tinned copper braid screen delivers mechanical robustness and strong EMI shielding for stable, noise-free signal transmission in electrically harsh environments.
Applications & Installation Environments
Designed for fixed indoor installation in dry or slightly humid conditions, the cable is suited to public buildings, hospitals, airports, tunnels, commercial complexes, and industrial facilities. As a shielded fire cable, it performs reliably where electrical noise, vibration, or physical strain are present.
Standards & Compliance
Manufactured to international requirements including EN 50200 and IEC 60331 (circuit integrity) and compliant with relevant flame-retardant testing, the LIHCH FE180 PH120 aligns with modern fire-safety specifications for signal and control circuits.
Why Specify ETK Kablo’s LIHCH FE180 PH120?
Choose this fire-resistant cable when your project demands fire-safety, low smoke, and EMI-protected signal continuity. ETK Kablo’s engineering and quality assurance deliver long-term reliability for safety-critical infrastructure.