| 1 – Conductor | : | Class 1 electrolytic solid copper (IEC 60228, DIN VDE 0295, EN 60228) |
| 2 – Insulation | : | Cross-linked polymer compound in ceramic form (VDE 0815) |
| 3 – Stranding | : | Insulations are stranded into pairs, four pairs are stranded together into groups, groups are stranded in layers. |
| 4 – Wrapping | : | Polyester tape, glass yarn tape |
| 5 – Outer Jacket | : | UV resistant halogen-free outer jacket. RAL 2008 (Orange) |
| Conductor Diameter | Conductor Resistance Ω/km (20 °C) | Insulation Resistance (@500V DC) MΩ/km | Mutual Capacitance nF/km | Operating Voltage V DC | Test Voltage (@ 1 minute) V DC |
|---|---|---|---|---|---|
| 0.60 mm | 130.0 | 100 | 100 | 300 | 1000 |
| 0.80 mm | 73.2 | 100 | 100 | 300 | 1000 |
| 1.00 mm | 44.6 | 100 | 100 | 300 | 1000 |
| 1.50 mm² | 24.6 | 100 | 100 | 300 | 1000 |
| 2.50 mm² | 15.1 | 100 | 100 | 300 | 1000 |
| Smoke Density Test | Corrosive Gas Test | Halogen-free Test | Flame Propagation Test | Flame Retardancy Test |
|---|---|---|---|---|
| IEC 61034-2, VDE 0482-1034-2, BS EN 61034-2 | IEC 60754-2, VDE 0482-267-2-3, BS EN 50267-2-3 | IEC 60754-1, VDE 0482-267-2-1, BS EN 50267-2-1 | IEC 60332-3-24, VDE 0482-332-3-24, EN 60332-2-24 | IEC 60332-1-2, VDE 0482-332-1-2, BS EN 60332-1-2 |
| Circuit Integrity Test (FE180) | Circuit Integrity with Shock Test (PH120) | Cable System Circuit Integrity Test (E30 / E60 / E90) |
|---|---|---|
| IEC 60331-21 | EN 50200, VDE 0482-200, BS EN 50200 | DIN 4102-12 E30 / E60 / E90 |
| Part Number | Pair Count | Conductor Diameter (mm) | Approx. Cable Diameter (mm) | Copper Weight (kg/km) | Approx. Weight (kg/km) | Packing Lengths (m) |
|---|---|---|---|---|---|---|
| 3.651.1.4.3.0060.0.0001 | 1 | 0,6 | 4,3 | 5,4 | 22 | 100/500/1000 |
| 3.651.1.4.3.0060.0.0002 | 2 | 0,6 | 4,9 | 10,7 | 34 | 100/500/1000 |
| 3.651.1.4.3.0060.0.0003 | 3 | 0,6 | 6,4 | 16,1 | 50 | 100/500/1000 |
| 3.651.1.4.3.0060.0.0004 | 4 | 0,6 | 7,6 | 21,5 | 63 | 100/500/1000 |
| 3.651.1.4.3.0060.0.0005 | 5 | 0,6 | 8 | 26,8 | 75 | 100/500/1000 |
| 3.651.1.4.3.0060.0.0006 | 6 | 0,6 | 9,7 | 32,2 | 91 | 100/500/1000 |
| 3.651.1.4.3.0060.0.0008 | 8 | 0,6 | 9,9 | 42,9 | 109 | 100/500/1000 |
| 3.651.1.4.3.0060.0.0010 | 10 | 0,6 | 10,3 | 53,6 | 129 | 100/500/1000 |
| Part Number | Pair Count | Conductor Diameter (mm) | Approx. Cable Diameter (mm) | Copper Weight (kg/km) | Approx. Weight (kg/km) | Packing Lengths (m) |
|---|---|---|---|---|---|---|
| 3.651.1.4.3.0080.0.0001 | 1 | 0,8 | 5 | 9,5 | 31 | 100/500/1000 |
| 3.651.1.4.3.0080.0.0002 | 2 | 0,8 | 5,9 | 19 | 50 | 100/500/1000 |
| 3.651.1.4.3.0080.0.0003 | 3 | 0,8 | 7,6 | 28,6 | 72 | 100/500/1000 |
| 3.651.1.4.3.0080.0.0004 | 4 | 0,8 | 9,1 | 38,1 | 95 | 100/500/1000 |
| 3.651.1.4.3.0080.0.0005 | 5 | 0,8 | 9,5 | 47,7 | 111 | 100/500/1000 |
| 3.651.1.4.3.0080.0.0006 | 6 | 0,8 | 11,5 | 57,2 | 134 | 100/500/1000 |
| 3.651.1.4.3.0080.0.0008 | 8 | 0,8 | 12 | 76,2 | 166 | 100/500/1000 |
| 3.651.1.4.3.0080.0.0010 | 10 | 0,8 | 12,4 | 95,3 | 199 | 100/500/1000 |
| Part Number | Pair Count | Conductor Diameter (mm) | Approx. Cable Diameter (mm) | Copper Weight (kg/km) | Approx. Weight (kg/km) | Packing Lengths (m) |
|---|---|---|---|---|---|---|
| 3.651.1.4.3.0100.0.0001 | 1 | 1 | 5,7 | 14,9 | 42 | 100/500/1000 |
| 3.651.1.4.3.0100.0.0002 | 2 | 1 | 6,6 | 29,7 | 67 | 100/500/1000 |
| 3.651.1.4.3.0100.0.0003 | 3 | 1 | 8,6 | 44,7 | 98 | 100/500/1000 |
| 3.651.1.4.3.0100.0.0004 | 4 | 1 | 10,4 | 59,6 | 129 | 100/500/1000 |
| 3.651.1.4.3.0100.0.0005 | 5 | 1 | 10,8 | 74,5 | 151 | 100/500/1000 |
| 3.651.1.4.3.0100.0.0006 | 6 | 1 | 13,4 | 89,3 | 187 | 100/500/1000 |
| 3.651.1.4.3.0100.0.0008 | 8 | 1 | 13,8 | 119,1 | 230 | 100/500/1000 |
| 3.651.1.4.3.0100.0.0010 | 10 | 1 | 14,3 | 148,9 | 276 | 100/500/1000 |
| Part Number | Pair Count | Conductor Diameter (mm) | Approx. Cable Diameter (mm) | Copper Weight (kg/km) | Approx. Weight (kg/km) | Packing Lengths (m) |
|---|---|---|---|---|---|---|
| 3.651.1.4.3.0150.0.0001 | 1 | 1,5 | 6,6 | 27,4 | 61 | 100/500/1000 |
| 3.651.1.4.3.0150.0.0002 | 2 | 1,5 | 7,8 | 54,8 | 104 | 100/500/1000 |
| 3.651.1.4.3.0150.0.0003 | 3 | 1,5 | 10,2 | 82,6 | 152 | 100/500/1000 |
| 3.651.1.4.3.0150.0.0004 | 4 | 1,5 | 12,3 | 110,1 | 200 | 100/500/1000 |
| 3.651.1.4.3.0150.0.0005 | 5 | 1,5 | 12,9 | 137,7 | 238 | 100/500/1000 |
| 3.651.1.4.3.0150.0.0006 | 6 | 1,5 | 16,1 | 165,2 | 296 | 100/500/1000 |
| 3.651.1.4.3.0150.0.0008 | 8 | 1,5 | 16,7 | 220,2 | 376 | 100/500/1000 |
| 3.651.1.4.3.0150.0.0010 | 10 | 1,5 | 17,3 | 275,3 | 448 | 100/500/1000 |
| Part Number | Pair Count | Conductor Diameter (mm) | Approx. Cable Diameter (mm) | Copper Weight (kg/km) | Approx. Weight (kg/km) | Packing Lengths (m) |
|---|---|---|---|---|---|---|
| 3.651.1.4.3.0250.0.0001 | 1 | 2,5 | 7,6 | 44,9 | 87 | 100/500/1000 |
| 3.651.1.4.3.0250.0.0002 | 2 | 2,5 | 8,8 | 89,7 | 148 | 100/500/1000 |
| 3.651.1.4.3.0250.0.0003 | 3 | 2,5 | 11,7 | 135,2 | 218 | 100/500/1000 |
| 3.651.1.4.3.0250.0.0004 | 4 | 2,5 | 14,3 | 180,3 | 288 | 100/500/1000 |
| 3.651.1.4.3.0250.0.0005 | 5 | 2,5 | 15,1 | 225,3 | 350 | 100/500/1000 |
| 3.651.1.4.3.0250.0.0006 | 6 | 2,5 | 18,7 | 270,4 | 428 | 100/500/1000 |
| 3.651.1.4.3.0250.0.0008 | 8 | 2,5 | 19,5 | 360,5 | 549 | 100/500/1000 |
| 3.651.1.4.3.0250.0.0010 | 10 | 2,5 | 20,1 | 450,6 | 661 | 100/500/1000 |
| Bending Radius | Temperature Range Operating |
|---|---|
| 10xD mm | -40°C ~ +70°C |
JE-HH Bd FE180 / E30-E60-E90 / PH120 Fire Resistant Cable
ETK Kablo’s JE-HH Bd FE180 / E30-E60-E90 / PH120 Fire Resistant Cable is a halogen-free, unshielded fire-resistant cable engineered to maintain circuit continuity and system integrity during a fire. Built for life-safety applications, this LSOH (Low Smoke Zero Halogen) cable minimizes toxic smoke while delivering proven fire survival performance in safety-critical infrastructure.
Fire Performance & Safety
With certified ratings of FE180 (conductor functionality up to 180 minutes) and PH120 (circuit integrity for 120 minutes under flame and mechanical stress), this cable supports E30 / E60 / E90 installation integrity when installed with appropriately tested support systems. The result is a fire-safe cable solution trusted where continuous power or signaling is essential.
Design & Construction
Constructed with solid copper conductors and an LSOH sheath, the JE-HH Bd is unshielded for simple, reliable routing in fixed indoor installations. It is suitable for cable trays, risers, or conduits in dry or humid areas across tunnels, public buildings, hospitals, airports, commercial facilities and other high-risk environments.
Applications
Ideal for fire alarm systems, voice evacuation (PA/VA), emergency lighting, BMS and control circuits, and power supply lines to fire-critical devices—whenever fire-safe cables are mandated by code or specification.
Standards & Compliance
Manufactured and tested according to IEC 60331 and EN 50200 for circuit integrity under fire, supporting modern building fire-safety requirements for fire-resistant cables.
Comparison: Fire-Resistant Cable Options
Choose the construction that fits your EMI environment and installation requirements:
| Model | Shielding | Fire Ratings | Typical Use Case | Sheath / Halogen |
|---|---|---|---|---|
| JE-HH Bd FE180 / E30-E60-E90 / PH120 Fire Resistant Cable | Unshielded | FE180, PH120, supports E30/E60/E90 with tested support systems | General fire-resistant power/signal runs in low-EMI areas (alarm loops, PA/VA, emergency lighting) | LSZH / Halogen-free |
| JE-H(St)H Bd FE180 PH120 Fire Resistant Cable | Overall foil screen (St) | FE180, PH120 | Fire-resistant circuits in moderate EMI environments needing additional shielding | LSZH / Halogen-free |
| JE-H(St)H Bd FE180 / E30-E60-E90 / PH120 | Overall foil screen (St) | FE180, PH120, supports E30/E60/E90 with tested support systems | Fire-resistant circuits in EMI-sensitive areas requiring both shielding and E-class installation integrity | LSZH / Halogen-free |
Why Choose ETK Kablo?
Specify JE-HH Bd FE180 / E30-E60-E90 / PH120 Fire Resistant Cable when you need an unshielded, halogen-free fire-safe cable that combines certified fire survival with long-term reliability. For EMI-rich environments, select the corresponding JE-H(St)H Bd shielded variants.