| 1 – Conductor | : | Class 1 electrolytic solid copper (IEC 60228, DIN VDE 0295, EN 60228) |
| 2 – Insulation | : | Cross-linked polymer compound in ceramic form (VDE 0815) |
| 3 – Stranding | : | Insulations are stranded into pairs, four pairs are stranded together into groups, groups are stranded in layers. |
| 4 – Wrapping | : | Polyester tape, glass yarn tape |
| 5 – Outer Jacket | : | UV resistant halogen-free outer jacket. RAL 2008 (Orange) |
| Conductor Diameter | Conductor Resistance Ω/km (20 °C) | Insulation Resistance (@500V DC) MΩ/km | Mutual Capacitance nF/km | Operating Voltage V DC | Test Voltage (@ 1 minute) V DC |
|---|---|---|---|---|---|
| 0.60 mm | 130.0 | 100 | 100 | 300 | 1000 |
| 0.80 mm | 73.2 | 100 | 100 | 300 | 1000 |
| 1.00 mm | 44.6 | 100 | 100 | 300 | 1000 |
| 1.50 mm² | 24.6 | 100 | 100 | 300 | 1000 |
| 2.50 mm² | 15.1 | 100 | 100 | 300 | 1000 |
| Smoke Density Test | Corrosive Gas Test | Halogen-free Test | Flame Propagation Test | Flame Retardancy Test |
|---|---|---|---|---|
| IEC 61034-2, VDE 0482-1034-2, BS EN 61034-2 | IEC 60754-2, VDE 0482-267-2-3, BS EN 50267-2-3 | IEC 60754-1, VDE 0482-267-2-1, BS EN 50267-2-1 | IEC 60332-3-24, VDE 0482-332-3-24, EN 60332-2-24 | IEC 60332-1-2, VDE 0482-332-1-2, BS EN 60332-1-2 |
| Circuit Integrity Test (FE180) | Circuit Integrity with Shock Test (PH120) | Cable System Circuit Integrity Test (E30 / E60 / E90) |
|---|---|---|
| IEC 60331-21 | EN 50200, VDE 0482-200, BS EN 50200 | DIN 4102-12 E30 / E60 / E90 |
| Part Number | Pair Count | Conductor Diameter (mm) | Approx. Cable Diameter (mm) | Copper Weight (kg/km) | Approx. Weight (kg/km) | Packing Lengths (m) |
|---|---|---|---|---|---|---|
| 3.651.1.4.3.0060.0.0001 | 1 | 0,6 | 4,3 | 5,4 | 22 | 100/500/1000 |
| 3.651.1.4.3.0060.0.0002 | 2 | 0,6 | 4,9 | 10,7 | 34 | 100/500/1000 |
| 3.651.1.4.3.0060.0.0003 | 3 | 0,6 | 6,4 | 16,1 | 50 | 100/500/1000 |
| 3.651.1.4.3.0060.0.0004 | 4 | 0,6 | 7,6 | 21,5 | 63 | 100/500/1000 |
| 3.651.1.4.3.0060.0.0005 | 5 | 0,6 | 8 | 26,8 | 75 | 100/500/1000 |
| 3.651.1.4.3.0060.0.0006 | 6 | 0,6 | 9,7 | 32,2 | 91 | 100/500/1000 |
| 3.651.1.4.3.0060.0.0008 | 8 | 0,6 | 9,9 | 42,9 | 109 | 100/500/1000 |
| 3.651.1.4.3.0060.0.0010 | 10 | 0,6 | 10,3 | 53,6 | 129 | 100/500/1000 |
| Part Number | Pair Count | Conductor Diameter (mm) | Approx. Cable Diameter (mm) | Copper Weight (kg/km) | Approx. Weight (kg/km) | Packing Lengths (m) |
|---|---|---|---|---|---|---|
| 3.651.1.4.3.0080.0.0001 | 1 | 0,8 | 5 | 9,5 | 31 | 100/500/1000 |
| 3.651.1.4.3.0080.0.0002 | 2 | 0,8 | 5,9 | 19 | 50 | 100/500/1000 |
| 3.651.1.4.3.0080.0.0003 | 3 | 0,8 | 7,6 | 28,6 | 72 | 100/500/1000 |
| 3.651.1.4.3.0080.0.0004 | 4 | 0,8 | 9,1 | 38,1 | 95 | 100/500/1000 |
| 3.651.1.4.3.0080.0.0005 | 5 | 0,8 | 9,5 | 47,7 | 111 | 100/500/1000 |
| 3.651.1.4.3.0080.0.0006 | 6 | 0,8 | 11,5 | 57,2 | 134 | 100/500/1000 |
| 3.651.1.4.3.0080.0.0008 | 8 | 0,8 | 12 | 76,2 | 166 | 100/500/1000 |
| 3.651.1.4.3.0080.0.0010 | 10 | 0,8 | 12,4 | 95,3 | 199 | 100/500/1000 |
| Part Number | Pair Count | Conductor Diameter (mm) | Approx. Cable Diameter (mm) | Copper Weight (kg/km) | Approx. Weight (kg/km) | Packing Lengths (m) |
|---|---|---|---|---|---|---|
| 3.651.1.4.3.0100.0.0001 | 1 | 1 | 5,7 | 14,9 | 42 | 100/500/1000 |
| 3.651.1.4.3.0100.0.0002 | 2 | 1 | 6,6 | 29,7 | 67 | 100/500/1000 |
| 3.651.1.4.3.0100.0.0003 | 3 | 1 | 8,6 | 44,7 | 98 | 100/500/1000 |
| 3.651.1.4.3.0100.0.0004 | 4 | 1 | 10,4 | 59,6 | 129 | 100/500/1000 |
| 3.651.1.4.3.0100.0.0005 | 5 | 1 | 10,8 | 74,5 | 151 | 100/500/1000 |
| 3.651.1.4.3.0100.0.0006 | 6 | 1 | 13,4 | 89,3 | 187 | 100/500/1000 |
| 3.651.1.4.3.0100.0.0008 | 8 | 1 | 13,8 | 119,1 | 230 | 100/500/1000 |
| 3.651.1.4.3.0100.0.0010 | 10 | 1 | 14,3 | 148,9 | 276 | 100/500/1000 |
| Part Number | Pair Count | Conductor Diameter (mm) | Approx. Cable Diameter (mm) | Copper Weight (kg/km) | Approx. Weight (kg/km) | Packing Lengths (m) |
|---|---|---|---|---|---|---|
| 3.651.1.4.3.0150.0.0001 | 1 | 1,5 | 6,6 | 27,4 | 61 | 100/500/1000 |
| 3.651.1.4.3.0150.0.0002 | 2 | 1,5 | 7,8 | 54,8 | 104 | 100/500/1000 |
| 3.651.1.4.3.0150.0.0003 | 3 | 1,5 | 10,2 | 82,6 | 152 | 100/500/1000 |
| 3.651.1.4.3.0150.0.0004 | 4 | 1,5 | 12,3 | 110,1 | 200 | 100/500/1000 |
| 3.651.1.4.3.0150.0.0005 | 5 | 1,5 | 12,9 | 137,7 | 238 | 100/500/1000 |
| 3.651.1.4.3.0150.0.0006 | 6 | 1,5 | 16,1 | 165,2 | 296 | 100/500/1000 |
| 3.651.1.4.3.0150.0.0008 | 8 | 1,5 | 16,7 | 220,2 | 376 | 100/500/1000 |
| 3.651.1.4.3.0150.0.0010 | 10 | 1,5 | 17,3 | 275,3 | 448 | 100/500/1000 |
| Part Number | Pair Count | Conductor Diameter (mm) | Approx. Cable Diameter (mm) | Copper Weight (kg/km) | Approx. Weight (kg/km) | Packing Lengths (m) |
|---|---|---|---|---|---|---|
| 3.651.1.4.3.0250.0.0001 | 1 | 2,5 | 7,6 | 44,9 | 87 | 100/500/1000 |
| 3.651.1.4.3.0250.0.0002 | 2 | 2,5 | 8,8 | 89,7 | 148 | 100/500/1000 |
| 3.651.1.4.3.0250.0.0003 | 3 | 2,5 | 11,7 | 135,2 | 218 | 100/500/1000 |
| 3.651.1.4.3.0250.0.0004 | 4 | 2,5 | 14,3 | 180,3 | 288 | 100/500/1000 |
| 3.651.1.4.3.0250.0.0005 | 5 | 2,5 | 15,1 | 225,3 | 350 | 100/500/1000 |
| 3.651.1.4.3.0250.0.0006 | 6 | 2,5 | 18,7 | 270,4 | 428 | 100/500/1000 |
| 3.651.1.4.3.0250.0.0008 | 8 | 2,5 | 19,5 | 360,5 | 549 | 100/500/1000 |
| 3.651.1.4.3.0250.0.0010 | 10 | 2,5 | 20,1 | 450,6 | 661 | 100/500/1000 |
| Bending Radius | Temperature Range Operating |
|---|---|
| 10xD mm | -40°C ~ +70°C |
JE-HH Bd FE180 PH120 Fire Resistant Cable
JE-HH Bd FE180 PH120 is an unscreened fire resistant cable for signal, communication and control circuits. It combines solid copper conductors, ceramic-forming cross-linked insulation and an orange, UV-resistant halogen-free outer jacket.
Part of ETK Kablo’s fire resistant cable range, this paired cable serves projects that require circuit integrity under defined fire test conditions. Select the conductor size and pair count to match the connected equipment and circuit requirements.
Unscreened Paired Cable for Signal and Control Circuits
The JE-HH Bd design groups insulated conductors into pairs and larger assemblies into bundles. Its applications include instrumentation, control engineering, indoor communication and sound systems where the project specifies a fire resistant cable.
This construction has no metallic screen. Where the circuit specification requires an overall foil screen, review the separate JE-H(St)H Bd fire resistant cable and its supporting technical documentation.
FE180, PH120 and E30-E60-E90 Requirements
The product datasheet lists FE180 circuit integrity and PH120 circuit integrity with mechanical shock. These designations refer to different test conditions; they are not interchangeable with flame retardancy or low-smoke performance.
E30, E60 and E90 concern the complete installed cable system, including the cable, supports and fixings. For a project requiring one of these classes, request the applicable system test documentation and installation instructions for the selected JE-HH Bd configuration. FE180 or PH120 alone does not establish an E-class installation.
For more detail, see ETK Kablo’s guide to FE180, PH120, E30, E60 and E90 cable ratings.
Selected JE-HH Bd Cable Sizes
The following table lists selected 0.8 mm conductor diameter configurations. For the full range, dimensions, weights and packing lengths, see the Types section on this page.
| Cable Size | Pair Count | Conductor Count | Conductor Diameter |
|---|---|---|---|
| JE-HH Bd FE180 PH120 1x2x0.8 | 1 | 2 | 0.8 mm |
| JE-HH Bd FE180 PH120 2x2x0.8 | 2 | 4 | 0.8 mm |
| JE-HH Bd FE180 PH120 3x2x0.8 | 3 | 6 | 0.8 mm |
| JE-HH Bd FE180 PH120 4x2x0.8 | 4 | 8 | 0.8 mm |
| JE-HH Bd FE180 PH120 5x2x0.8 | 5 | 10 | 0.8 mm |
| JE-HH Bd FE180 PH120 6x2x0.8 | 6 | 12 | 0.8 mm |
| JE-HH Bd FE180 PH120 8x2x0.8 | 8 | 16 | 0.8 mm |
| JE-HH Bd FE180 PH120 10x2x0.8 | 10 | 20 | 0.8 mm |
Frequently Asked Questions
What does JE-HH Bd 2x2x0.8 mean?
It identifies two pairs, containing four conductors in total, with a conductor diameter of 0.8 mm. The final value denotes diameter, not a cross-section of 0.8 mm².
Does this cable include a foil or braid screen?
No. JE-HH Bd is the unscreened construction. A specification that requires screening needs a suitable screened product.
Does a halogen-free jacket guarantee circuit integrity?
No. Halogen-free and low-smoke properties concern material behaviour during fire. FE180 and PH120 address circuit integrity under their respective test conditions.
Request a Quotation
Contact ETK Kablo for a JE-HH Bd FE180 PH120 quotation. Include the pair count, conductor size, required length and project fire performance requirements. For E30, E60 or E90 installations, also specify the proposed support system and required documentation.