JE-H(St)H…Bd FE180 / E30-E60-E90 / PH120 Fire Resistant Cable

Product Code: JE-H(St)H...Bd FE180 / E30-E60-E90 / PH120

1 – Conductor:Class 1 electrolytic solid copper (IEC 60228, DIN VDE 0295, EN 60228)
2 – Insulation:Cross-linked polymer compound in ceramic form (VDE 0815)
3 – Stranding:Insulations are stranded into pairs, four pairs are stranded together into groups, groups are stranded in layers.
4 – Wrapping:Polyester tape, glass yarn tape
5 – Screen:Tinned copper earthing wire, Al/PET tape
6 – Outer Jacket:UV resistant halogen-free outer jacket. RAL 2008 (Orange)
Conductor
Diameter
Conductor Resistance
Ω/km
(20 °C)
Insulation
Resistance
(@500V DC)
MΩ/km
Mutual Capacitance

nF/km
Operating
Voltage

V DC
Test Voltage

(@ 1 minute)
V DC
0.60 mm130.01001003001000
0.80 mm73.21001003001000
1.00 mm44.61001003001000
1.50 mm²24.61001003001000
2.50 mm²15.11001003001000
Smoke Density TestCorrosive Gas TestHalogen-free TestFlame Propagation TestFlame Retardancy Test
IEC 61034-2,
VDE 0482-1034-2,
BS EN 61034-2
IEC 60754-2,
VDE 0482-267-2-3,
BS EN 50267-2-3
IEC 60754-1,
VDE 0482-267-2-1,
BS EN 50267-2-1
IEC 60332-3-24,
VDE 0482-332-3-24,
EN 60332-2-24
IEC 60332-1-2,
VDE 0482-332-1-2,
BS EN 60332-1-2
Circuit Integrity Test
(FE180)
Circuit Integrity with Shock Test
(PH120)
Cable System Circuit Integrity Test
(E30 / E60 / E90)
IEC 60331-21EN 50200,
VDE 0482-200,
BS EN 50200
DIN 4102-12 E30 / E60 / E90
Part NumberPair CountConductor Diameter (mm)Approx. Cable Diameter (mm)Copper Weight (kg/km)Approx. Weight (kg/km)Packing Lengths (m)
3.650.1.4.3.1080.0.000110,85.414.338100/500/1000
3.650.1.4.3.1080.0.000220,86.223.854100/500/1000
3.650.1.4.3.1080.0.000330,87.933.480100/500/1000
3.650.1.4.3.1080.0.000440,89.542.9103100/500/1000
3.650.1.4.3.1080.0.000550,89.852.4119100/500/1000
3.650.1.4.3.1080.0.000660,811.962144100/500/1000
3.650.1.4.3.1080.0.000880,812.381178100/500/1000
3.650.1.4.3.1080.0.0010100,812.8100.1208100/500/1000
Bending RadiusTemperature Range
Operating
10xD mm-40°C ~ +70°C

JE-H(St)H Bd FE180 Cable for E30, E60 and E90 Systems

JE-H(St)H Bd FE180 E30-E60-E90 PH120 is a screened, halogen-free cable for signal and control circuits with specified fire performance requirements. It combines solid copper conductors, twisted pairs, ceramic-forming insulation and an overall aluminium/polyester foil screen. The orange LSZH jacket completes this product in ETK Kablo’s fire resistant cable range.

FE180, PH120 and E30-E60-E90 Performance

FE180 describes cable integrity for 180 minutes under the specified fire test conditions. PH120 describes circuit integrity for 120 minutes under fire and mechanical shock testing according to EN 50200.

E30, E60 and E90 refer to 30, 60 and 90 minutes of functional integrity for a tested cable installation system under DIN 4102-12. These classifications apply to the cable together with the specified supports, fixings and installation arrangement. For an E90 installation, select the cable size and mounting system covered by the relevant test documentation.

For a detailed comparison, read our guide to FE180, PH120, E30, E60 and E90 cable ratings.

Screened Signal and Control Applications

Typical applications include instrumentation, control engineering, industrial electronics, indoor communication and sound systems. For fire detection or emergency communication circuits, check the connected equipment requirements and project specification when selecting the cable.

The overall foil screen and tinned copper drain wire help manage electromagnetic interference when correctly terminated and grounded. Low smoke, halogen-free materials address smoke and corrosive gas characteristics separately from circuit integrity performance.

JE-H(St)H Bd Cable Sizes: 1x2x0.8 to 10x2x0.8

The table below lists the 0.8 mm conductor configurations shown in the Types section. In 2x2x0.8, the first number means two pairs, the second means two conductors per pair, and 0.8 is the conductor diameter in millimetres. It is not a 0.8 mm² cross-section.

Cable SizePair CountConductor CountConductor Diameter (mm)
JE-H(St)H Bd FE180 E30-E60-E90 PH120 1x2x0.8120.8
JE-H(St)H Bd FE180 E30-E60-E90 PH120 2x2x0.8240.8
JE-H(St)H Bd FE180 E30-E60-E90 PH120 3x2x0.8360.8
JE-H(St)H Bd FE180 E30-E60-E90 PH120 4x2x0.8480.8
JE-H(St)H Bd FE180 E30-E60-E90 PH120 5x2x0.85100.8
JE-H(St)H Bd FE180 E30-E60-E90 PH120 6x2x0.86120.8
JE-H(St)H Bd FE180 E30-E60-E90 PH120 8x2x0.88160.8
JE-H(St)H Bd FE180 E30-E60-E90 PH120 10x2x0.810200.8

For cable dimensions, weights and packing lengths, see the Types section on this page. Confirm the required E30, E60 or E90 installation configuration when ordering.

Frequently Asked Questions

What is JE-H(St)H Bd FE180 E90 2x2x0.8?

This designation describes a two-pair cable with four solid conductors, each 0.8 mm in diameter, and the stated FE180 requirement. E90 refers to its use within the appropriately tested cable installation system. Include PH120 and the required system documentation in your specification where applicable.

Is JE-H(St)H Bd 1x2x0.8 available for an E30 project?

The product range includes a 1x2x0.8 configuration with one pair and two conductors. For an E30 project, confirm that this size and the proposed support and fixing arrangement fall within the relevant system test documentation.

Does FE180 automatically provide E90 performance?

No. FE180 concerns cable-level fire integrity. E90 concerns the functional integrity of the tested cable installation system. An FE180 designation alone does not establish E90 performance.

Request a JE-H(St)H Bd FE180 Quotation

Contact ETK Kablo with your required pair count, conductor diameter, cable length and FE180, PH120 or E30-E60-E90 requirements. For system-integrity applications, also provide the planned mounting arrangement and required test documentation.