LIH(St)CH FE180 PH120 Fire Resistant Cable

Product Code: LIH(St)CH FE180 PH120

1 – Conductor:Stranded electrolytic copper conductor (Class 5) (IEC 60228, EN 60228, DIN VDE 0295)
2 – Insulation:Cross-linked polymer compound in ceramic form (DIN 47100)
3 – Stranding:In layers
4 – Wrapping:Polyester tape, glass yarn tape
5 – Screen:Al/PET, tinned copper braiding
6 – Outer Jacket:UV resistant halogen-free outer jacket. RAL 2008 (Orange)
Conductor
Diameter
Conductor Resistance
Ω/km
(20 °C)
Insulation
Resistance
(@500V DC)
MΩ/km
Mutual Capacitance

nF/km
Operating
Voltage

V DC
Test Voltage

(@ 1 minute)
V DC
0.50 mm²39.01001003002000
0.75 mm²26.01001003002000
1.00 mm²19.51001003002000
1.50 mm²13.31001003002000
2.50 mm²8.01001003002000
Smoke Density TestCorrosive Gas TestHalogen-free TestFlame Propagation TestFlame Retardancy Test
IEC 61034-2,
VDE 0482-1034-2,
BS EN 61034-2
IEC 60754-2,
VDE 0482-267-2-3,
BS EN 50267-2-3
IEC 60754-1,
VDE 0482-267-2-1,
BS EN 50267-2-1
IEC 60332-3-24,
VDE 0482-332-3-24,
EN 60332-2-24
IEC 60332-1-2,
VDE 0482-332-1-2,
BS EN 60332-1-2
Circuit Integrity Test
(FE180)
Circuit Integrity with Shock Test
(PH120)
IEC 60331-21EN 50200,
VDE 0482-200,
BS EN 50200
Part NumberConductorCountConductor Diameter (mm²)Approx. Cable Diameter(mm)Copper Weight(kg/km)Approx. Weight (kg/km)Packing Lengths (m)
3.535.2.4.3.0050.0.000220,55,515,635100/500/1000
3.535.2.4.3.0050.0.000330,55,820,148100/500/1000
3.535.2.4.3.0050.0.000440,56,524,660100/500/1000
3.535.3.4.3.0050.0.000550,5729,172100/500/1000
3.535.3.4.3.0050.0.000660,57,534,884100/500/1000
3.535.3.4.3.0050.0.000770,57,539,287100/500/1000
3.535.3.4.3.0050.0.000880,58,143,8103100/500/1000
3.535.3.4.3.0050.0.000990,59,450,8120100/500/1000
3.535.3.4.3.0050.0.0010100,59,455,2124100/500/1000
3.535.3.4.3.0050.0.0012120,59,864,6142100/500/1000
3.535.3.4.3.0050.0.0014140,510,473,5161100/500/1000
3.535.3.4.3.0050.0.0016160,510,983,3178100/500/1000
3.535.3.4.3.0050.0.0018180,511,592,3202100/500/1000
3.535.3.4.3.0050.0.0019190,511,596,7205100/500/1000
3.535.3.4.3.0050.0.0020200,512,1102,5222100/500/1000
3.535.3.4.3.0050.0.0021210,512,1106,9223100/500/1000
3.535.3.4.3.0050.0.0024240,513,4123,1261100/500/1000
3.535.3.4.3.0050.0.0025250,513,4127,5275100/500/1000
3.535.3.4.3.0050.0.0027270,513,7136,3284100/500/1000
Part NumberConductorCountConductor Diameter (mm²)Approx. Cable Diameter(mm)Copper Weight(kg/km)Approx. Weight (kg/km)Packing Lengths (m)
3.535.2.4.3.0075.0.000220,756,12050100/500/1000
3.535.2.4.3.0075.0.000330,756,526,661100/500/1000
3.535.2.4.3.0075.0.000440,75733,475100/500/1000
3.535.3.4.3.0075.0.000550,757,741,292100/500/1000
3.535.3.4.3.0075.0.000660,758,348,5102100/500/1000
3.535.3.4.3.0075.0.000770,758,355,1112100/500/1000
3.535.3.4.3.0075.0.000880,759,162,6135100/500/1000
3.535.3.4.3.0075.0.000990,7510,470,5153100/500/1000
3.535.3.4.3.0075.0.0010100,7510,477,4158100/500/1000
3.535.3.4.3.0075.0.0012120,7510,991,3182100/500/1000
3.535.3.4.3.0075.0.0014140,7511,4105,4208100/500/1000
3.535.3.4.3.0075.0.0016160,7512120231100/500/1000
3.535.3.4.3.0075.0.0018180,7512,7135,7264100/500/1000
3.535.3.4.3.0075.0.0019190,7512,7142,4269100/500/1000
3.535.3.4.3.0075.0.0020200,7513,4150,5292100/500/1000
3.535.3.4.3.0075.0.0021210,7513,4157,1294100/500/1000
3.535.3.4.3.0075.0.0024240,7514,7177,2334100/500/1000
3.535.3.4.3.0075.0.0025250,7514,7183,8352100/500/1000
3.535.3.4.3.0075.0.0027270,7515,1197,2368100/500/1000
Part NumberConductorCountConductor Diameter (mm²)Approx. Cable Diameter(mm)Copper Weight(kg/km)Approx. Weight (kg/km)Packing Lengths (m)
3.535.2.4.3.0100.0.0002216,523,556100/500/1000
3.535.2.4.3.0100.0.0003316,93270100/500/1000
3.535.3.4.3.0100.0.0004417,541,387100/500/1000
3.535.3.4.3.0100.0.0005518,249,8107100/500/1000
3.535.3.4.3.0100.0.0006618,959,6126100/500/1000
3.535.3.4.3.0100.0.0007718,967,9132100/500/1000
3.535.3.4.3.0100.0.0008819,877,3158100/500/1000
3.535.3.4.3.0100.0.00099111,286,5180100/500/1000
3.535.3.4.3.0100.0.001010111,294,7186100/500/1000
3.535.3.4.3.0100.0.001212111,7112,2215100/500/1000
3.535.3.4.3.0100.0.001414112,4132,4248100/500/1000
3.535.3.4.3.0100.0.001616113150,3276100/500/1000
3.535.3.4.3.0100.0.001818113,7166312100/500/1000
3.535.3.4.3.0100.0.001919113,7174,3318100/500/1000
3.535.3.4.3.0100.0.002020114,4182,8343100/500/1000
3.535.3.4.3.0100.0.002121114,4191346100/500/1000
3.535.3.4.3.0100.0.002424115,9218,7397100/500/1000
3.535.3.4.3.0100.0.002525115,9227419100/500/1000
3.535.3.4.3.0100.0.002727116,3243,7434100/500/1000
Part NumberConductorCountConductor Diameter (mm²)Approx. Cable Diameter(mm)Copper Weight(kg/km)Approx. Weight (kg/km)Packing Lengths (m)
3.535.2.4.3.0150.0.000221,57,133,971100/500/1000
3.535.2.4.3.0150.0.000331,57,546,890100/500/1000
3.535.2.4.3.0150.0.000441,58,259,9111100/500/1000
3.535.3.4.3.0150.0.000551,5974,3138100/500/1000
3.535.3.4.3.0150.0.000661,59,788,3163100/500/1000
3.535.3.4.3.0150.0.000771,59,7101,2173100/500/1000
3.535.3.4.3.0150.0.000881,510,7114,8206100/500/1000
3.535.3.4.3.0150.0.000991,512,3129,1234100/500/1000
3.535.3.4.3.0150.0.0010101,512,3142243100/500/1000
3.535.3.4.3.0150.0.0012121,512,9171,2285100/500/1000
3.535.3.4.3.0150.0.0014141,513,6198,5326100/500/1000
3.535.3.4.3.0150.0.0016161,514,2223,3363100/500/1000
3.535.3.4.3.0150.0.0018181,515250,3412100/500/1000
3.535.3.4.3.0150.0.0019191,515263,1421100/500/1000
3.535.3.4.3.0150.0.0020201,515,8277,6456100/500/1000
3.535.3.4.3.0150.0.0021211,515,8290,5461100/500/1000
3.535.3.4.3.0150.0.0024241,517,6330,1531100/500/1000
3.535.3.4.3.0150.0.0025251,517,6342,9560100/500/1000
3.535.3.4.3.0150.0.0027271,518368,9582100/500/1000
Part NumberConductorCountConductor Diameter (mm²)Approx. Cable Diameter(mm)Copper Weight(kg/km)Approx. Weight (kg/km)Packing Lengths (m)
3.535.2.4.3.0250.0.000222,58,251,296100/500/1000
3.535.2.4.3.0250.0.000332,58,773125100/500/1000
3.535.2.4.3.0250.0.000442,59,797162100/500/1000
3.535.3.4.3.0250.0.000552,510,7119,9205100/500/1000
3.535.3.4.3.0250.0.000662,511,7145,3246100/500/1000
3.535.3.4.3.0250.0.000772,511,7166,7262100/500/1000
3.535.3.4.3.0250.0.000882,512,8189,7313100/500/1000
3.535.3.4.3.0250.0.000992,514,9211,8357100/500/1000
3.535.3.4.3.0250.0.0010102,514,9233,2373100/500/1000
3.535.3.4.3.0250.0.0012122,515,5276,3433100/500/1000
3.535.3.4.3.0250.0.0014142,516,4320,9497100/500/1000
3.535.3.4.3.0250.0.0016162,517,2364,3556100/500/1000
3.535.3.4.3.0250.0.0018182,518,2409,7632100/500/1000
3.535.3.4.3.0250.0.0019192,518,2431,1648100/500/1000
3.535.3.4.3.0250.0.0020202,519,2453,4700100/500/1000
3.535.3.4.3.0250.0.0021212,519,2474,8709100/500/1000
3.535.3.4.3.0250.0.0024242,521,4546815100/500/1000
3.535.3.4.3.0250.0.0025252,521,4567,5863100/500/1000
3.535.3.4.3.0250.0.0027272,521,8614901100/500/1000
Bending RadiusTemperature Range
Operating
10xD mm-40°C ~ +70°C

LIH(St)CH FE180 PH120 Foil and Braid Screened Cable

LIH(St)CH FE180 PH120 is a fire resistant signal and control cable with a combined aluminium/polyester foil and tinned copper braid screen. It uses flexible Class 5 copper conductors, ceramic-forming insulation and an orange halogen-free outer jacket. ETK Kablo offers this construction within its fire resistant cable range for projects requiring both screening and specified circuit integrity performance.

Combined Foil and Copper Braid Screening

The Al/PET foil and tinned copper braid form an overall screen around the insulated cores. These cores are stranded in layers, rather than arranged as individually screened pairs. Correct screen termination and grounding help the installation control electromagnetic interference.

Typical applications include instrumentation, control engineering, industrial electronics, indoor communication, sound systems, security and fire alarm circuits. Select the conductor count and cross-section to match the equipment, circuit length and project requirements.

FE180, PH120 and Halogen-Free Materials

FE180 describes cable integrity for 180 minutes under the specified fire test conditions. PH120 describes circuit integrity for 120 minutes under fire and mechanical shock testing according to EN 50200. These classifications represent laboratory performance and do not guarantee complete system operation for the same duration in every fire.

The low smoke, halogen-free materials address separate fire performance requirements. Product documentation lists IEC 61034-2 for smoke density, IEC 60754-1 and IEC 60754-2 for halogen and corrosive gas characteristics, and IEC 60332-1-2 and IEC 60332-3-24 for flame propagation performance.

Selected LIH(St)CH FE180 PH120 Cable Sizes

The table below lists selected configurations from the product range. For the full range, cable dimensions, weights and packing lengths, see the Types section on this page.

Cable SizeConductor CountConductor Cross-section (mm²)
LIH(St)CH FE180 PH120 2×0.50 mm²20.50
LIH(St)CH FE180 PH120 4×0.50 mm²40.50
LIH(St)CH FE180 PH120 2×0.75 mm²20.75
LIH(St)CH FE180 PH120 4×0.75 mm²40.75
LIH(St)CH FE180 PH120 7×0.75 mm²70.75
LIH(St)CH FE180 PH120 12×0.75 mm²120.75
LIH(St)CH FE180 PH120 2×1.00 mm²21.00
LIH(St)CH FE180 PH120 4×1.00 mm²41.00
LIH(St)CH FE180 PH120 4×1.50 mm²41.50
LIH(St)CH FE180 PH120 4×2.50 mm²42.50

Frequently Asked Questions

How does LIH(St)CH differ from LIH(St)H and LIHCH?

LIH(St)CH FE180 PH120 combines foil and tinned copper braid screening. The separate LIH(St)H FE180 PH120 cable uses foil screening with a drain wire, while LIHCH FE180 PH120 uses a tinned copper braid screen. These are distinct products with different screening constructions.

Is the copper braid a steel armor layer?

No. The tinned copper braid is part of the electrical screen. This product does not include steel wire armor.

What does 2×0.75 mm² mean?

It identifies two insulated conductors, each with a cross-section of 0.75 mm². The value describes conductor area, not diameter. It does not describe a two-pair cable.

Does FE180 PH120 also establish E90 performance?

No. E90 concerns a tested cable installation system, including its supports and fixings. The published specification for this product lists FE180 and PH120, but does not list an E90 classification.

Request a LIH(St)CH FE180 PH120 Quotation

Contact ETK Kablo with your required conductor count, cross-section, total length and installation conditions. Include the project fire test requirements and any supporting documentation needed for product selection.